background image

#3  TEST COCK

#4  TEST COCK

#2  SHUT-OFF

         VALVE

LOW SIDE BLEED

NEEDLE VALVE

       

LOW SIDE HOSE

NOTE: BY-PASS OMITTED FOR CLARITY

(FOR BY-PASS TESTING REFER TO MAINTENANCE

INSTRUCTIONS FOR MODEL 350D)

#2  TEST COCK

#1  TEST COCK

(ON OPPOSITE

SIDE OF VALVE)

#1  SHUT-OFF

VALVE

HIGH SIDE BLEED

NEEDLE VALVE

HIGH SIDE HOSE

VENT HOSE

TEST NO. 2 - TIGHTNESS OF #2 CHECK VALVE

REQUIREMENT:

The static pressure drop across check valve #2 shall be at 

least 1.0 psid. If test cock #4 is not at the highest point of 

the check valve body, then a vertical tube must be installed 

on test cock #4 so that it rises to the top of the check valve 

body.

PROCEDURE: 

1.  Attach hose from the high side of the test kit to the #3 

test cock.

2.  Open test cock #3 and bleed all air from the hose 

and gauge by opening the high side bleed needle 

valve. Close high side bleed needle valve. If a tube is 

attached to test cock #4, open test cock #4 to fill the 

tube. Close test cock #4. Close #1 shut-off valve.

3.  Hold gauge at same level as test cock #4 or water 

level in tube. Slowly open test cock #4. Record the 

static pressure drop across check valve #2 after 

gauge reading stabilizes and water stops running out 

of test cock #4.

4.  Close all test cocks, slowly open shut-off valve #1 & 

#2 and remove test equipment.

2

MODEL 950XLTDABF Double Check Detector Assembly

Testing Procedures

Equipment Required: Differential pressure gauge test kit.

TEST NO. 1 - TIGHTNESS OF #1 CHECK VALVE

REQUIREMENT:

The static pressure drop across check valve #1 shall be at 

least 1.0 psid. If test cock #3 is not at the highest point of 

the check valve body, then a vertical tube must be installed 

on test cock #3 so that it rises to the top of the check valve 

body.

PROCEDURE:

1.  Slowly open all 4 test cocks to remove any foreign 

material and attach fittings.

2.  Attach hose from the high side of the test kit to the #2 

test cock.

3.  Open test cock #2 and bleed all air from the hose 

and gauge by opening the high side bleed needle 

valve. Close high side bleed needle valve. If a tube is 

attached to test cock #3, open test cock #3 to fill the 

tube. Close test cock #3. Close #2 shut-off valve then 

close the #1 shut-off valve.

4.  Hold gauge at same level as test cock #3 or water 

level in tube. Slowly open test cock #3. Record the 

static pressure drop across check valve #1 after 

gauge reading stabilizes and water stops running out 

of test cock #3.

5.  Close all test cocks, open shut-off valve #1 and re-

move test equipment.

ZURN WILKINS

1747 Commerce Way, Paso Robles, CA 93446 Phone:

855-663-9876

 Fax:805-238-5766

®

www.zurn.com

Содержание 950XLTDABF

Страница 1: ...or damage to the device The installation location mustbekeptabove32 F Allthe basic installation instructions apply PLACING THE MODEL 950XLTDABF IN SERVICE 1 Start with both shut off valves closed Slowly open the inlet shut off valve until the backflow preventer is com pletely pressurized 2 When the unit has been pressur ized vent any trapped air by slightly opening each of the four test cocks 3 Sl...

Страница 2: ...t cock 4 4 Close all test cocks slowly open shut off valve 1 2 and remove test equipment 2 MODEL 950XLTDABF Double Check DetectorAssembly Testing Procedures Equipment Required Differential pressure gauge test kit TEST NO 1 TIGHTNESS OF 1 CHECK VALVE REQUIREMENT The static pressure drop across check valve 1 shall be at least 1 0 psid If test cock 3 is not at the highest point of the check valve bod...

Страница 3: ... reassembly for proper operation refer to TESTING PROCEDURES SERVICING CHECK VALVES 1 Close inlet and outlet shut off valves 2 Open No 2 No 3 and No 4 test cocks to release pres sure from valve 3 Unscrew check valve cover using appropriate sized wrench CAUTION COVER IS SPRING LOADED Toavoidinjury holdcoverdownfirmlywithonehand while unscrewing 4 Remove cover spring and poppet assembly 5 Inspect th...

Страница 4: ...iling governmental industry standards and codes and upon following these installation instructions Failure to do so releases ZURN WILKINS of any liability that it might otherwise have with respect to that device Such failure could also result in an improperly functioning device Rated Flow Established by approval agencies Troubleshooting Performance Characteristics BLACK SWITCH POSITION VALVE FULL ...

Отзывы: