ZXR10 T8000 Hardware Installation Guide (Cluster)
Physical Parameter
ZXR10 T8000
Backup mode
4+4
Rated power per machine
5100W
Rated input voltage
200V - 240V
Input frequency range
50Hz - 60Hz
Rated output voltage
-53.5V
Rated output current
NA
AC power supply
Rated output power per
module
2000W/module
Number of horizontal fan
modules
2
Number of fans in horizontal
fan modules
9
Backup mode
1+1
Variable rate control mode
Supported
Cooling system
Heat dissipation
13923 BTU/hour
Temperature
-5
℃
- 50
℃
Humidity
5% - 90%
Operational
environment
requirements
Altitude
<5000m
Temperature
-40°C - +70°C
Storage environment
requirements
Humidity
0 - 95%
Grounding resistance
The grounding resistance in case of joint
grounding is less than 5Ω.
Note:
If the altitude is below 1800m, the long-term operating temperature is 40°C and the
short-term operating temperature is 50°C.
If the altitude is above 1800m, the maximum temperature of the operating environment
decreases by 0.5
℃
for every 100-meter increase in altitude. The maximum supported
altitude is 5000m.
1.4 Cluster Installation Flow
This topic describes how to install ZXR10 T8000 cluster 1+4 and cluster 2+8.
The
installation flow of the two clusters is basically the same, as shown in
Figure 1-5
.