24
Working torque
– Check and, if necessary, set the value of the working torque 50 – 100 % in program DMS2, which you change only
after consultation with the armature manufacturer.
Tripping in end-limit positions
– Check and, if necessary, set the way of tripping in the end-limit positions::
– Torque
– position O
– position Z
– position O + Z
End-limit positions – working stroke
– Position Z
– Shift to position Closed either manually or by means of menu Motor in program DMS2.
– The actuator can only be controlled by means of the program if no torque is induced. The torque should be left
manually.
– Press push-button Z to confirm consent with the record.
– Position O
– Shift to position Open either manually or by means of menu Motor in program DMS2.
– The actuator can only be controlled by means of the program if no torque is induced. The torque should be left
manually.
– Press push-button O to confirm consent with the record.
Autocalibration
– The autocalibration can only be started by means of the program if no torque is induced. The torque should be left manually.
– The autocalibration is started by push-button Start in program DMS2.
– Wait until the autocalibration is completed; information on its course is signalized next to push-button Start.
Other parameters
Check and, if necessary, change other parameters:
Control signal
4 – 20 mA
20 – 4mA
0 – 20 mA
20 – 0 mA
2 position
Bus
Insensitivity
1 – 1 0 %
Function SAFE
Open
Close
Stop
To position
Active SAFE
O V
230 V
Time of blocking torque
in end-limit positions
0 – 20 s
Position of blocking torque
in end-limit positions
1 – 10 %
Output of position signal
4 – 20 mA
20 – 4 mA
Function READY
Switched off
Warning
Errors
Warning or error
- Combined error
Errors or not Errors or warning
Torque “O” or “Z”
remote
or not remote
Switched off
Position O
Position Z
Torque O
Torque Z
Torque and position O Torque and position Z
Relay 1 – 4
Opening
Closing
Motion
Position
position N
Local control
Emote control
Control switched off
Torque O/Z
Motion - blinker
Position Relay 1 – 4
0 – 100 %
Note:
SAFE – input information on the error of an external device can be set so that the actuator would respond as to
its own error.
Содержание MODACT MTNED 15
Страница 1: ...Type numbers 52 442 52 443 Electric Linear Pull rod actuators 11 18 MOUNTING INSTRUCTIONS ...
Страница 2: ...ZPA Pečky a s is certified company in accordance with ISO 9001 as amended ...
Страница 28: ...28 Terminal board of DMS2 Analog Terminal board of DMS2 Profibus ...
Страница 44: ...44 NOTES ...
Страница 45: ...45 NOTES ...
Страница 46: ...46 NOTES ...