12
Overview of MENU
BROWSING THROUGH MENU
– The setting regime is entered by pressing and keeping depressed push-button
MENU for at least 2 s; LED1
is then lit on.
– Shortly press
MENU to select the basic MENU – menu M1 to M8
(LED1 signalizes the menu number);
by
short pressing of P, O, C they are entered
(LED2 signalizes particular parameter).
– Shortly press P to select required value of the parameter. In case the parameter can be set to several
values, they are changed by short pressing of P
(number of blinking of LED2 indicates its value).
Keep
pressing of P to record the chosen parameter; the record is confirmed by lighting on of LED2.
– Shortly press
MENU to gradually set the required menu and parameters.
– After setting all required parameters, exit the setting menu by pressing and keeping depressed push-button
MENU for at least 2 s. The setting menu will also be left in case that no push-button is pressed within
1 minute.
MENU 1 – Setting of tripping torques
– After entering the menu by means of push-button C or O, select required torque.
– Shortly press P to select the set value of the parameter 50 – 100 %
(5 – 10 blinking of LED2)
and keep pressing
push-button P to store the parameter to memory.
MENU 2 – Setting function of signalling relays
– Basic setting of the signalling relays is SZ 1 % and SO 99 % of stroke.
– n case different setting is required, it can be changed after shifting the actuator to required position by means of
push-button C or O.
– Using push-button P, perform basic setting SZ 1 % and SO 99 % of stroke.
MENU 3 – Setting of blocking of torque in end-limit positions
– Shortly press P to select the set value of blocking time 0 – 20 s
(0 – 20 blinking of LED2)
and keep pressing push-
button P to store the parameter to memory.
– Keep pressing push-button C to store actual position for blocking torque on the side Closed to memory.
– Keep pressing push-button O to store actual position for blocking torque on the side Open to memory.
MENU 4 – Setting transducer characteristics
– Shortly press P to select the value 4 – 20 mA – 1x blinking of LED2 or 20 – 4 mA – 2x blinking of LED2, and keep
pressing push-button P to store the parameter to memory.
Other menus only serve for board setting in version Control
MENU 5 – Setting control signal in 3P regulation
– Shortly press P to select value 4 – 20 mA
- 1x blinking of LED2,
or 20 – 4 mA
- 2x blinking of LED2,
or 0 – 20 mA
- 3x blinking of LED2,
or 20 – 0 mA
- 4x blinking of LED2
and keep pressing push-button P to store the parameter to memory.
MENU 6 – Setting insensitivity in three-position regulation
– Shortly press P to select value 1 – 10 %
(1 – 10x blinking of LED2)
and keep pressing push-button P to store the
parameter to memory.
MENU 7 – Response in case of losing control signal in three-position regulation
– Shortly press P to select value OPEN
- 1x blinking of LED2,
or CLOSE
- 2x blinking of LED2,
or STOP
- 3x blinking of LED2,
and keep pressing push-button P to store the parameter to memory.
Содержание MODACT MTNED 15
Страница 1: ...Type numbers 52 442 52 443 Electric Linear Pull rod actuators 11 18 MOUNTING INSTRUCTIONS ...
Страница 2: ...ZPA Pečky a s is certified company in accordance with ISO 9001 as amended ...
Страница 28: ...28 Terminal board of DMS2 Analog Terminal board of DMS2 Profibus ...
Страница 44: ...44 NOTES ...
Страница 45: ...45 NOTES ...
Страница 46: ...46 NOTES ...