background image

10

Resistance transmitted and position indicator setting

To set the position indicator proceed as follows: With the output shaft in the 

“closed”

 position slide out the gate 51 

(Figure 8)

 by pressing it towards the transmitter, disengaging it from the pinion 49 

(Figure 5).

 Then, turn the gate clockwise 

to the stop which forms a column under the signalling unit. Then, re-engage the gate with the pinion 49. The transmitter 
pointer should point to 0°. If it does not, move the gate 51 back before its stop and depress the gate 55. This will release 
the transmitter pinion and the transmitter pointer can be set near the mark 0° on the transmitter scale so that their teeth 
engage properly with each other, once the gate 55 gets engaged with the pinion. Carefully turn the transmitter shaft to 
make sure their clinching is correct. Then, we can again slide out the gate 51 from engagement, pushing it more vigorously 
towards the stop 

(with the transmitter pointer moved to the mark 0° the pinion will slide through). 

Then, re-engage the gate 

51 with the pinion 49. In this position, the oval openings in the toothed gates go parallel with the oval opening in the main 
control board 67 

(Figure 2). 

Now the transmitter is adjusted for the “closed” position. Then, loosen the screw 64 

(Figure 8), 

position the shifting lever 65 towards the transmitter to the stop point and retighten the screw 64.

Re-set the actuator to the 

“open”

 position; the transmitter pointer is re-set to a position between 0° and 160°. Release 

screw 64 and turn aligning lever 65 anticlockwise until the transmitter indicator reaches 160°C sign. Subsequently re-
tighten screw 64 again and drop quick-drying ink on it to prevent it from releasing. Thus the transmitter is set to 

“open”

 

position. The position indicator is mounted on the resistance transmitter axis 42

 (Figure 8) 

with the screw 41. This screw 

will be loosened in its 

“open”

 position, and the indicator is turned, so that the mark 100 on the indicator scale 40 would 

coincide  with  the  color  dot  on  the  view  port  in  the  control  box  lid.  Subsequently,  tighten  screw  41  and  secure  it  in 
tightened position by dropping quick-drying varnish on it.

II.  Vishay resistance transmitter

Alternatively, actuators 

MOA can be equipped with a Vishay resistance transmitter. This transmitter has a shaft 

led out on one side, with double wheel 73, consisting of toothed gears A and B, fixed on the end of the shaft. The 
principle  of  drive  and  adjustment  of Vishay  transmitter  is  identical  to  current  transmitter  CPT  1AAE. The  only 
difference consists in sizes of toothed gears A and B of double wheel 73, and thus also in table including values 
for working stroke setting.

Setting of position resistive transmitter

First of all you must set the appropriate gear from the output shaft of the actuator to transmitter shaft according to the 

required working stroke of the actuator shown in the following table.

Configuration  is  performed  using  the  adjustable  wheel  K3  in  the  gearbox  of  the  signal  unit  as  per  the  previous 

paragraph b). Further, you must bring the necessary gear of the double wheel, affixed on the transmitter shaft, into 
meshing position. The wheel with the smaller diameter is marked A, the larger wheel is marked B.

The adjustment is made by moving the spacers 72 either under the transmitter bracket 

(wheel A is engaged)

 or above 

the  transmitter  bracket 

(wheel  B  is  engaged).

 This  is  done  at  the  position  where  the  transmitter  bracket  is  the  most 

distanced from the gearbox.

Wheel on the transmitter – gears  

Description: 

68 – Resistance transmitter
69 – Transmitter bracket
70 – Locking screw
71 – Contact plate
72 – Spacers
73 – Double wheel
74 – Spacer rings

B

A

73

72

70

71

74

69

K3

68

70

71

A

B

73

K3

68

69

72

74

Содержание 52 020

Страница 1: ...Type numbers 52 020 52 026 Electric multi turn rotary actuators for nuclear power stations outside active zones 2 20 INSTALLATION INSTALLATION INSTRUCTIONS INSTRUCTIONS...

Страница 2: ...ZPA Pe ky a s is certified company in accordance with ISO 9001 as amended...

Страница 3: ...grease located on the power box on the hand wheel side Actuators with oil filling position is limited only by the electric motor axis inclination max 15 below horizontal line This prevents possible c...

Страница 4: ...rting resistance or current transmitter are provided by mechanical groups units These are located on the control board Figure 2 fitted inside the control box Control units are differentiated by functi...

Страница 5: ...able Segment 23 is intended for closing direction segment 24 for opening direction Explanatory notes 5 Resistance position transmitter Vishay 11 Local position indicator 12 Torque tripping unit 13 Sig...

Страница 6: ...is closer to number 10 indicates the setting point of maximum tripping torque the other line identifies the setting point of minimum torque The torque control unit must never be set up in a way that...

Страница 7: ...oltages with different values or phases must not be led to the contacts of one micro switch Fig 4 Signalling unit Explanatory notes K1 Gear K2 Driving wheel K3 Shifting wheel 47 Locking screw of adjus...

Страница 8: ...ansmitter it is always necessary to re align the actuator output shaft to a position in which the micro switches are supposed to switch or in which the required position of the transmitter adjuster is...

Страница 9: ...ious values of working stroke of actuator and thus also for various turning of cam shaft in signalling unit the transmitter turning angle and the local position indicator turning angle is always 160 T...

Страница 10: ...n indicator is mounted on the resistance transmitter axis 42 Figure 8 with the screw 41 This screw will be loosened in its open position and the indicator is turned so that the mark 100 on the indicat...

Страница 11: ...the resistance begins to rise up to the resistance value corresponding to the end position open 50 to 98 max Thereby the transmitter is adjusted Local position indicator Local position indicator Figur...

Страница 12: ...e actuator to transmitter shaft according to the required working stroke of the actuator shown in the following table on page 9 Configuration is performed using the adjustable wheel K3 in the gearbox...

Страница 13: ...ge must lie between 18 to 25 V and must in no case exceed 30 V this would result in transmitter destruction Then connect the transmitter so that the source positive pole is connected to the positive p...

Страница 14: ...n turn it by 90 degrees in any direction b Turn set screw 56 in Z arrow direction until the cam 57 pushes the spring of micro switch PZ 63 d Turn tripping rod 58 by 90 Tripping rod will slip out again...

Страница 15: ...nying documentation and the purchase order Possible discrepancies defects or damage must be immediately reported to supplier If the packed actuator is not installed immediately after receipt it must b...

Страница 16: ...to a position where the signalling switch SZ is supposed to change over Adjust SZ switch according to instructions specified under point 5b 5 Turn the actuator output shaft by the required number of r...

Страница 17: ...P 80 motor car gearbox oil Oil quantities for individual type numbers Adapter of actuator 52 026 is to be filled with fat PM MOGUL LV2 3 quantity 3 kg 11 TROUBLESHOOTING 1 The actuator in its end posi...

Страница 18: ...40 2 250 7 MOA 160 9 52 021 YX42S 9 1 98 63 37 MOA 160 16 52 021 YX52S 16 1 56 65 40 MOA 160 25 52 021 YX62S 63 160 25 120 69 41 MOA 160 40 52 021 YX12S 40 1 36 70 43 MOA 160 63 52 021 YX22S 63 1 22 7...

Страница 19: ...2 8 5 0 1LE1002 0CD3 0 12 625 0 82 1 64 31 0 68 1 7 2 0 3 06 1LE1002 0CC3 0 25 860 0 98 2 15 52 0 71 2 0 2 2 5 6 6 0 1LE1001 0DC2 0 37 925 1 14 4 32 67 0 69 2 1 4 0 8 1 9 1LE1001 0DC3 0 55 935 1 65 7...

Страница 20: ...12 5 20 25 20 25 1 25 d4 h max 3 4 5 5 5 d7 40 60 80 100 120 h2 10 12 15 16 18 b2 H11 14 20 24 30 40 d6 30 41 5 53 72 72 d9 H8 20 30 40 50 60 16 min 55 76 97 117 127 t3 22 8 33 3 43 3 53 8 64 4 b4Js9...

Страница 21: ...52 025 2xxxS 52 025 3xxxS A B C D E max F G max H J K 290 90 300 78 344 228 572 160 99 120 305 360 120 328 92 469 228 697 200 144 376 435 145 382 123 560 258 818 250 190 440 523 178 442 153 745 298 10...

Страница 22: ...ot be subject to the overall force higher than indicated in the table 1000 2000 4000 6000 MODACT MOA actuator centre of gravity 52020 2022S 52022 2012S 52024 2042S 52025 2022S 52026 2002S 52020 3x22S...

Страница 23: ...14 mm 4x 11 13 290 260 315 150 Range 13 18 mm Range 10 14 mm 1x cable gland 4x cable gland 1x cable gland Range 6 12 mm 52 020 52 021 52 025 52 022 52 024 52 026 Dimension Type number 44 60 90 98 35...

Страница 24: ...cts of one micro switch Contacts of the micro switches are drawn in the intermediate position Without position transmitter P1001 P1006 P1009 P1015 Position transmitter resistance 100 Position transmit...

Страница 25: ...tput signal of 4 20 mA The Annex includes technical data and instructions of the converter manufacturer which must be observed during assembly Setting procedure Set the actuator limit switches and the...

Страница 26: ...owledgeable personnel in accordance with section 5 of the Decree no 50 1978 Coll respectively 51 1978 Coll The 222 224 RIP converter 222 224 RIR is attached by sliding on the DIN TS35 rail First place...

Страница 27: ...midity 40 to 70 atmospheric pressure 84 to107 kPa protection IP 20 permissible conductor cross section 0 35 to 4 mm2 module width 22 5 mm box material NORYL box resistance to temperature dimensional s...

Страница 28: ...28 Lock 38 8 22 5 65 45 85...

Страница 29: ...29 Interconnection of actuators MOA and MOA OC with a Control block Example of connecting to the MOA actuator SWITCHING BLOCK Transformer 52 020 8 7 6 other 4 3 2 designs...

Страница 30: ...open MO J3 4 LZ position closed PZ J3 5 PZ common PZ MZ J3 6 MO torque open MO Connect J4 Block of local control J4 1 24 V control phase J4 2 D phase for remote regulator function J4 3 LZ phase for lo...

Страница 31: ...ver sealing 2327311038 Git seal ring 40x52x7 SN 029401 0 2 Sealing of output shaft in power transmission box 2327352066 Git seal ring 16x28x7 SN 029401 0 1 Handwheel shaft seal in the cast iron design...

Страница 32: ...1 Sealing of local position indicator glass 2327311037 Microswitch B 613 2 1 Microswitches SQT2 SQFT1 SQT1 SQC1 2337441070 Seal ring 125x110 SN 029280 2 1 Seal inserts with Git Seal rings in the power...

Страница 33: ...t sealing 2327352054 Microswitch B 613 2 1 Microswitches SQT2 SQFT1 SQT1 SQC1 2337441070 Seal ring 90x2 SN 029281 2 1 Sealing below torque spring cover 2327311081 Seal 16 22 224580840 2 Threaded cap s...

Страница 34: ...34 NOTES...

Страница 35: ...i turn actuators MODACT MO EEx MOED EEx Explosion proof electric multi turn actuators MODACT MOA Electric multi turn actuators for nuclear power stations application outside containment MODACT MOA OC...

Страница 36: ...tel 420 321 785 141 9 fax 420 321 785 165 420 321 785 167 e mail zpa zpa pecky cz ZPA Pe ky a s t 5 kv tna 166 289 11 PE KY Czech Republic www zpa pecky cz...

Отзывы: