PREMIER EX PLUS – OPERATION & INSTALLATION MANUAL
PAGE 15
DOCUMENT: GLT-MAN.115
ISSUE: 1 DATE: 22/8/05
AUTHOR: NRPJ
ANALOGUE VALUES (RETURN CODES)
When the Premier EX Plus is connected to an addressable loop, it will reply with an analogue value
depending on its condition. The following table shows what each analogue value means:-
ANALOGUE
VALUE
PANEL CONDITION
INDICATION ON CENTRAL
PANEL
0 BATTERY
FAULT
CHARGER FAULT
FAULT
1
ZONE 1 OPEN CIRCUIT FAULT
ZONE 1 SHORT CIRCUIT FAULT
FAULT
2
ZONE 2 OPEN CIRCUIT FAULT
ZONE 2 SHORT CIRCUIT FAULT
FAULT
3
BOTTLE OUTPUT OPEN CIRCUIT FAULT
BOTTLE OUTPUT SHORT CIRCUIT FLT
FAULT
4
1ST STAGE SND OPEN CIRCUIT FAULT
1ST STAGE SND SHORT CIRCUIT FAULT
2ND STAGE SND OPEN CIRCUIT FAULT
2ND STAGE SND SHORT CIRCUIT FAULT
FAULT
5
AUTO/MAUAL LINE O/C FAULT
HOLD/ABORT LINE O/C FAULT
MAUAL RELEASE LINE O/C FAULT
GAS FIRED LINE O/C FAULT
GAS FIRED LINE S/C FAULT
FAULT
16
NORMAL CONDITION – AUTOMATIC
NORMAL
17
NORMAL CONDITION – MANUAL
NORMAL
47 1
ST
STAGE ALARM – MANUAL START
PRE-ALARM
48
ZONE 1 – 1
ST
STAGE ALARM
PRE-ALARM
49
ZONE 2 – 1
ST
STAGE ALARM
PRE-ALARM
64 SECOND
STAGE
ALARM
ALARM.