![Zooper OPT1/4 Скачать руководство пользователя страница 15](http://html1.mh-extra.com/html/zooper/opt1-4/opt1-4_installation-manual_939574015.webp)
Optima
INSTALLATION MANUAL.
Approved Document No: GLT.MAN-109
PAGE 15
Issue : 1.2 Authorised: GH Date: 31/03/2004
11. PCB TERMINATION CONNECTIONS.
FS6
ZONE
VOLTAGE
500mA
FS4
SND1
150mA
FS3
En54 SUP
200mA
FS1
CHARGER
1.6A
FS5
SND2
150mA
MAIN
S F
USE
2A H
BC
CERA
MIC
1 2 3 4 5 6 7 8 9
FS7
SND1
150MA
FS8
SND2
150MA
FS2
BATTERY
1.6A
11.1 CONNECTIONS
Connection No Description
Use
1
ZONE 1 +&-
Connect to Zone 1
2
ZONE 2 +&-
Connect to Zone 2
3
ZONE 3 +&-
Connect to Zone 3
4
ZONE 4 +&-
Connect to Zone 4
5
ZONE 5 +&-
Connect to Zone 5
6
ZONE 6 +&-
Connect to Zone 6
7
ZONE 7 +&-
Connect to Zone 7
8
ZONE 8 +&-
Connect to Zone 8
9
SND 1 +&-
Connect to sounder circuit 1 (sirens/bells)
10
SND 2 +&-
Connect to sounder circuit 2 (sirens/bells)
11
AUX SUPPLY
200 mA Supply @ System voltage (29-31 V dc)
12
SND 3 +&-
Connect to sounder circuit 3 (sirens/bells)
13
SND 4 +&-
Connect to sounder circuit 4 (sirens/bells)
14
FIRE RELAY NO/CM/NC
Activates on fire (including test mode)
15
AC AC
Connected to transformer secondary (30VAC)
16
B & -
Connect 2 x 12V SLA batteries in SERIES (ie 24V)
17
CONN 1
20 way ribbon cable to display PCB
18
CONN 5
MAINS TERMINAL BLOCK
19
CONN 4
Connector for Add on Relay Board
11.2 FUSES
FUSE NO
DESCRIPTION
RATING
FS1
Charger Fuse
1.6A time delay 5 x 20mm glass
FS2
Battery Fuse
1.6A time delay 5 x 20mm glass
FS3
Aux Supply Fuse
200mA time delay 5 x 20mm glass
FS4
Sounder circuit 1
150mA time delay 5 x 20mm glass
FS5
Sounder circuit 2
150mA time delay 5 x 20mm glass
FS6
Zone Voltage Fuse
500mA time delay 5 x 20mm glass
FS7
Sounder circuit 3
150mA time delay 5 x 20mm glass
FS8
Sounder circuit 4
150mA time delay 5 x 20mm glass
INLET FUSE
Mains Protection Fuse
2A Quick Blow HBC 5 x 20mm ceramic