Zooper OPT1/4 Скачать руководство пользователя страница 11

Optima

 INSTALLATION MANUAL.  

 

 

 

 

 

Approved Document No: GLT.MAN-109

 

 

 

PAGE 11

 

Issue : 1.2         Authorised: GH      Date: 31/03/2004

 

 

 
6.2 NON LATCHING ZONES 
 
The optima panel has the option to configure zone 1 as a non-latching zone. This is done by snipping 
the jumper link SW1 with a small wire cutter WHEN THERE IS NO POWER APPLIED TO THE 
PANEL. 
 
When zone 1 is configured as non-latching, the panel will start the sounders & light zone 1 Fire LED 
on receiving an alarm signal, but it will not activate its fire relay. When the alarm signal is removed, 
the panel will automatically reset itself. 
 
The main use for using non latching zones is for linking 2 or more fire alarm panels. 
 

7. ZONE DISABLEMENT 

 

7.1 WHY USE ZONE DISABLEMENT 

 

To aid commissioning and assist routine maintenance checks, any of the zones or the sounder 
circuits can be disabled. 

 

When a zone (or sounder circuit) is disabled, the panel will not respond to any fault or fire signals it 
receives from that zone. This might be used if the system requires routine maintenance, and the 
customer needs the system to continue running, but doesn’t want spurious false alarms. 

 

The panel will respond in the usual manner to any events in any non-disabled zones. 

 
7.2 TO PROGRAMME ZONE (OR SOUNDERS) AS DISABLED 

 

Any number of zones (or the sounders) can be disabled, but it is good practice to only disable one 
zone at a time. 

 

1. 

Insert and turn control key to enabled position; 

 

2. 

Press Engineer switch and the GENERAL DISABLEMENT LED will come on (flashing fast); 

 

3. 

Press Scroll switch and the GENERAL DISABLEMENT LED will flash slowly. The panel is now 
in SELECT DISABLEMENT MODE. 

 

4. 

Press scroll button again. Zone 1 DISABLEMENT LED will be lit. Continue to press scroll until 
the desired Zone or sounder is lit.  Press the Engineer button. The GENERAL DISABLEMENT 
LED will be lit constantly indicating that this zone (or sounder) is now disabled. 

 

5. 

If more than one zone needs to be disabled, then press scroll again until the required zone is 
selected. 

 

6. 

If the panel needs to be taken out of SELECT DISABLEMENT MODE (eg to silence a fault on 
another part of the system), turn the keyswitch off, then back on again. 

 

7. 

Once all the work has been done the zones need to be enabled again. If the panel is still in 
SELECT DISABLEMENT MODE, jump to paragraph 8, otherwise, turn the keyswitch to 
controls enabled, press engineer button (GENERAL DISABLEMENT LED will flash fast). Press 
scroll and it will return to being on steady. The panel is now in SELECT DISABLEMENT MODE 

 

8. 

 Press the scroll button until the disabled zone has been selected. Press engineer button. 
Scroll to any other disabled zone and enable in the same way. When all zones are enabled 
again, the GENERAL DISABLEMENT LED will flash slowly. Turn the keyswitch to off to return 
the system to normal.  

 

Содержание OPT1/4

Страница 1: ...INSTALLATION MANUAL FIRE ALARM CONTROL PANEL COMPLIES WITH EN54 part 2 part 4 MEETS THE FUNCTIONAL REQUIREMENT OF BS EN 5839 part 1 ...

Страница 2: ...4 1 CONNECTING MAINS POWER 4 2 CONNECTING THE BATTERIES 5 FIELD DEVICE TERMINATION 9 5 1 TERMINATING THE DETECTION AND ALARM SOUNDER CIRCUITS 5 2 AUXILIARY INPUT AND OUTPUT TERMINATIONS 6 CONFIGURING THE PANEL 10 6 1 SOUNDER ACTIVATION DELAY 6 1 1 DECIDING TO USE A DELAY 6 1 2 TO SET A DELAY 6 1 3 DELAY INDICATION AND OVERRIDE 6 2 NON LATCHING ZONES 7 ZONE DISABLEMENT 10 7 1 WHY USE ZONE DISABLEME...

Страница 3: ...iced in accordance with our instructions and the relevant National Standards Contact the Fire Officer concerned with the property at an early stage in case he has any special requirements If in doubt read BS 5839 Pt 1 2002 Fire Detection and Alarm Systems for buildings Code of Practice for System Design Installation and Servicing available from the BSI or at your local reference library 1 5 EQUIPM...

Страница 4: ...M shielding when properly grounded at the panel Certain system specifications may demand the use of a particular type of cable and due regard should be paid to this fact Depending on the environment the cables may need mechanical protection such as a conduit 2 2 MAINS WIRING RECOMMENDATIONS The Mains supply to the FACP is fixed wiring using Fire resisting 3 core cable Between 1 mm and 2 5mm or a s...

Страница 5: ...is page Other makes of detector will have different connections but in general they are wired in one of 2 ways SPLIT NEGATIVE IN OUT to same terminal IN to stripe side of continuity diode OUT to non stripe side of continuity diode Or SPLIT POSITIVE IN to non stripe side of continuity diode OUT to stripe side of continuity diode IN OUT to same terminal Some makes of detector will connect the ve to ...

Страница 6: ...device is connected to the fault relay Typical auxiliary output wiring NO CM NC FAULT RELAY FAULT INDICATION DEVICE NOTE THE NC CONTACT IS OPEN WHEN THERE IS NO FAULT Trigger I P NO CM NC FIRE RELAY AUTO DIALER Trigger I P NO CM NC FIRE RELAY NO CM NC FAULT RELAY OUTSTATION FIRE INPUT FAULT INPUT TO ADDRESSABLE FIRE ALARM PANEL LOOP LOOP The termination for the above inputs must be as indicated on...

Страница 7: ...ed but subsequently not used it should be covered up The 230Va c Mains cable must be fed into the enclosure via one of the cable entries at the top right corner of the back box Refer to Connecting the Mains on Page 8 3 2 FIXING THE BACK BOX TO THE WALL Figure 2 Plan view inside the enclosure without PCBs Side view for surface flush installation Wall Mount Flush Mount 12 x 19mm grommet cable entrie...

Страница 8: ...otected by a quick blow 20mm 2A HBC fuse Also known as HRC The incoming mains cable should be kept separate from the zone cables to help minimise mains interference MAKE SURE ANY SPARE ENTRY HOLES ARE COVERED WITH THE PLASTIC GROMMETS PROVIDED It is advisable to apply power to the panel before connecting any devices to check for correct operation and to familiarise yourself with the fire alarm pan...

Страница 9: ...6a For detailed detector and alarm circuit wiring diagrams please refer to pages 4 and 5 MAINS TO TRANSFORMER PRIMARY CONN 27 INLET MAINS SUPPLY INTERNAL WIRING Brass Glands FS6 ZONE VOLTAGE 500mA FS4 SND1 150mA FS3 En54 SUP 200mA FS1 CHARGER 1 6A FS5 SND2 150mA FS7 SND1 150MA FS8 SND2 150MA FS2 BATTERY 1 6A Figure 6 Detector and Sounder Circuit Connection 5 2 AUXILIARY INPUT AND OUTPUT TERMINATIO...

Страница 10: ...te ON OFF OFF OFF 2 minutes OFF ON OFF OFF 3 minutes ON ON OFF OFF 4 minutes OFF OFF ON OFF 5 minutes ON OFF ON OFF 6 minutes OFF ON ON OFF 7 minutes ON ON ON OFF 8 minutes OFF OFF OFF ON 9 minutes ON OFF OFF ON 1 4 3 2 ON EG The above example would have a delay of 6 minute 6 1 3 DELAY INDICATION AND OVERRIDE If a delay is set the fire panel will light the General Disablement LED and Delay DEL LED...

Страница 11: ...sabled but it is good practice to only disable one zone at a time 1 Insert and turn control key to enabled position 2 Press Engineer switch and the GENERAL DISABLEMENT LED will come on flashing fast 3 Press Scroll switch and the GENERAL DISABLEMENT LED will flash slowly The panel is now in SELECT DISABLEMENT MODE 4 Press scroll button again Zone 1 DISABLEMENT LED will be lit Continue to press scro...

Страница 12: ... or turn the control key switch to off position to exit test mode 9 GENERAL FAULT FINDING 9 1 ZONE FAULTS Open circuit faults will be indicated by zone s fault LED flashing In case of a short circuit fault then the Zone s Fault LED will be accompanied by the Short Circuit Fault LED In both cases the internal Fault Buzzer will sound and the General Fault LED will be lit The Zone Faults are non latc...

Страница 13: ...Voltage The charging voltage should be 28 4V off load at 20o C If it has been altered reset using potentiometer VR1 5 Overcharged Batteries Remove the batteries and measure the voltage If it is reading over 27 4 then the batteries are overcharged Try to run the panel on batteries only for half an hour or so to try to discharge the batteries If this doesn t solve the problem replacement batteries w...

Страница 14: ... Detector 0 0001 Amp 100 µA Typical Example A system comprises of 20 ionisation detectors 14 bells and the required standby is 24 hours It will need to operate in alarm for hour Calculate the battery size required TALM 0 5 Hr IALM 14 x 0 025 0 35A This assumes the bell current is 25 mA Most alarm Devices show their operating current TSBY 24 Hr IQP 0 048A IQZ 20 x 0 00005 0 001A the quiescent curre...

Страница 15: ...e 29 31 V dc 12 SND 3 Connect to sounder circuit 3 sirens bells 13 SND 4 Connect to sounder circuit 4 sirens bells 14 FIRE RELAY NO CM NC Activates on fire including test mode 15 AC AC Connected to transformer secondary 30VAC 16 BATTERY Connect 2 x 12V SLA batteries in SERIES ie 24V 17 CONN 1 20 way ribbon cable to display PCB 18 CONN 5 MAINS TERMINAL BLOCK 19 CONN 4 Connector for Add on Relay Boa...

Страница 16: ...LTAGE 24V DC NOMINAL 18 32 V SYSTEM VOLTAGE RIPPLE 2V PK PK MAX CHARGER SIZE UP TO 7AH in 24 Hours ZONE VOLTAGE 21V DC NOMINAL 20 22 5V SOUNDER ALARM OUTPUTS 4 x 150mA 29V DC Nominal AUXILIARY FAULT OUTPUT Via add on relay PCB AUXILIARY FIRE OUTPUT 1 x RELAY SELV 1A MAX NUMBER OF ZONES 1 2 4 6 8 MAXIMUM ZONE CAPACITY 32 DEVICES PER ZONE MAXIMUM ZONE RESISTANCE 70 ohms AUXILIARY SUPPLY 200mA 29 V d...

Отзывы: