INSTALLATION

 

 

1. 

Cut a 4-inch (102-millimeter) opening in one side of the air 

duct at the location selected. Ensure the opening is cut fully to 

the top and bottom air duct seams. 

2. 

Slide the damper into the cut opening of the air duct. Ensure 

the electric actuator is mounted toward the top of the air duct. 

3. 

Secure  the  damper  mounting  plate  to  the  air  duct  with  the 

sheet metal zip screws provided. 

 

Side Mount: 

CHECKOUT

 

 

To  checkout  the  operation  of  the  dampers  the  control 

panel  needs  to  be  operating.   It  is  recommended  that 
each damper be checked before installing into the duct. 

 

To  check  the  damper,  plug  the  damper  into  a  zone  on 
the  control  panel.   Each  zone  of  the  panel  has  an  LED 
that will be 

Green 

when the damper is to be 

open

.  When 

the  panel  LED  is  off,  the  damper  will  

close  

and  the 

damper LED will turn 

RED

 

All  dampers  are  100%  factory  tested  with  the  cord 
provided with each damper.

 

 
 
 
 
 
 
 
 
 

 

OPEN        CLOSE 

The  damper  shaft  is  square 
however  the  motor  has  a 
small  triangular  shape  that 
also indicates the  position of 
the damper.  If the LED does 
not light, this will indicate the 
damper  is  either  opening  or 
closing. The damper may be 
closed and the LED not lit Red 
as  the  damper  may  have 
stopped  short  of  full  closed 
due  to  the  roundness  of  the 
damper.

 

Bottom Mount: 

 

 

TROUBLESHOOTING

 

If the damper LED does not light and the motor is not moving when 

plugged  into  the  control  panel,  unplug  and  retry  plugging  in 

again.   Until the motor moves and the LED lights.    Make sure 

the cord is not pinched or broken. 

 

The  motor  is  powered  by  12VDC  from  the  panel.      Check  the 
connector on the panel for 12VDC as shown below. 

 

MOTOR  PLUG

 

The  power to  the  dampers 
can  be  checked  with  a 
voltmeter             measuring 

12VDC.           Check      the 

 

and    any    wire    the    same 
way    by    checking    the 
inside    negative    pair   of 
wires  with  the  outside 
positive pair of wires. 

 

+12VDC

 

 

VDC 

 
 
 

 

-12VDC

 

 

VDC 

 

POSITIVE  (+) 

NEGATIVE  (-)

 

POSITIVE  (+) 
NOT  USED

 

 

DAMPER  OPEN 

MOTOR  PLUG 

NOT  USED 

POSITIVE  (+)

 

NEGATIVE  (-)

 

POSITIVE  (+) 

NOT  USED

 

DAMPER  CLOSED 