BPE24 Installation Instructions #BPE24 

© 2021 ZONEFIRST 

 

 

FORM BPE 

 

 

 

Control Panel Features 

 
 

The  Bypass  Eliminator  24

  (Model  BPE24)  Control  is  an 

interface between a ZONEFIRST Zone Control Panel and its 
zone dampers.  The BPE24 is used to eliminate the need for 
a  traditional  separate  by-pass  duct  and  damper  directed 
back  into  the  return  duct.   The BPE24 can ONLY be used 
with 24V Power Open/Power Closed Dampers and control 
panels.   
 
The  BPE24  uses  an  air  sensor  in  the  duct  system  on  the 
supply side and before all zone dampers so it can monitor 
the systems static pressure, whenever the blower is running.  
The  zone  dampers  are  now  wired  directly  into  the  BPE24 
and  not  the  zone  control  panel.    The  BPE24  has  4  zone 
inputs  where the damper outputs of the zone control panel 
will  plug-in  on  the BPE24. The zone control panel controls 
the zone dampers through the BPE24.    
 
The BPE24 will, on an increase in static pressure in the duct 
system, modulate the closed dampers to gradually open to 

relieve the air pressure back below the high set-point.  When 
this occurs the zone dampers will stop.      
 
 
INSTALLATION 
The BPE24 can be mounted against flush surface and should 

be  located  within  10’ of where the pressure sensor tube is 

placed  in  the  duct.    Ideally  if  mounted  next  to  the  zone 
control  panel  this  will  minimize  the  length  of  wires for the 
interconnection of the panels for the zone dampers.   
 
It  is  recommended  that the panel be mounted to a wall or 
return plenum and NOT on the furnace or plenum where it 
will  be  in  contact with the high heating temperatures.  The 
panel  can  be  located  in  an  attic  space  or  in  an  enclosed 
cabinet of a rooftop unit, provided the panel is enclosed and 
not in direct exposure to the elements.   
 
The cover easily removes from the case by pulling firmly and 
separating  the  cover  from  the  case  exposing  the  circuit 

LCD Menu Screen 
 System Mode Indicator 
LED 

24VAC Transformer 
Terminals 

Menu 
Configuration 
Buttons 

Output to Zone 
Dampers 

Zone Damper input  
Connections from 
zone board 

Pressure Input 

Содержание By-Pass Eliminator 24 BPE24

Страница 1: ...Pass Eliminator 24 Model BPE24 For use with 24V Power Open PowerClosed Damper Motors and Control Panels Only Installation and Operating Instructions ControllingYour Comfort Room by Room F o l l o w u s o n ...

Страница 2: ... in the duct system modulate the closed dampers to gradually open to relieve the air pressure back below the high set point When this occurs the zone dampers will stop INSTALLATION The BPE24 can be mounted against flush surface and should be located within 10 of where the pressure sensor tube is placed in the duct Ideally if mounted next to the zone control panel this will minimize the length of w...

Страница 3: ...er the Lower Limit menu from the main status display press SW2 and using SW1 and SW2 you can raise or lower the Lower Limit Once you have finished setting the lower limit the menu will automatically exit after 5 seconds back to the main screen Dead Band There is a minimum 0 10 WC dead band between the upper and lower limits that insures there is a sufficient pressure range that can be maintained f...

Страница 4: ... check the transformer and the power supply to it Zone s Not Closing If a zone is not closing and there is an active HVAC call it may be that there is an excessive amount of air being bypassed into the zone End all HVAC calls and using the damper test button on the Main Controller you can check to see if the dampers are properly cycling Damper Motor Checkout Procedure To check out the dampers the ...

Страница 5: ... Eliminator 24 Wiring Diagram From respective Zone Damper Connections on Zone Control Board To 24V AC on Zone Panel 24V Power Open Power Closed Dampers NOTE If there is a Specific zone that should not be used to relieve air wire zone damper directlyto zone panel ...