7

© Copyright 2013 Zoeller Co. All rights reserved.

5" (12.7 cm) MIN.

Y

1 1/2" (3.8 cm) MIN.

7" (17.8 cm)

6" (15.2 cm) MIN.

2" (5 cm) MIN.

Y

7" (17.8 cm)

   STEP 9      

INSTALLATION OF ADDITIONAL FIXTURES

 

9.1)  In order to add fixtures, a 3” diameter hole must be drilled into the side of the pump chamber using the spotting 

template located on page 11.

  9.2)  Figure 9.1 shows the location on the pump chamber which can be used for adding additional fixtures.

  

CAUTION

 

Do not plumb into the vertical ribs located on the front left corner of the pump chamber.

  9.3)  Affix the spotting template on the desired location and center the punch hole center. Use a 3” diameter hole saw 

to drill through pump chamber. NOTE: 

Model 101 is preassembled. Use caution when drilling into tank. Be 

sure to remove drilled plastic material from tank.

  9.4)  Insert a 2” rubber pipe seal (included) into the 3” hole and lubricate the inside diameter with soapy water to allow 

for ease of pipe insertion.

  9.5)  Insert pipe through seal approximately ¾” into tank.
  9.6)  Refer to Figures 9.2 - 9.5 for Typical installation of Tubs & Lavatories.

SK1589

Check local codes for discharge and 

vent sizing and installation.

Figure 9.1

NOTE:

  The bottom of the additional fixture 3" diameter hole must be 

5" or 6" minimum above the base of the tank depending upon which 

side of the tank is selected. Refer to drawing above. Cut out spotting 

template on page 11. 

Do not plumb into “crosshatched” area.

   STEP 8      

INSTALLATION OF TOILET

  NOTE: Only use the Wax Seal provided with the Floor Flange Extender Kit.

  8.1)  Free standing Installation (No subflooring)

   

1) 

Only 1 wax toilet bowl gasket required.

   

2) 

Install wax toilet bowl gasket, and toilet as described on the back of the gasket carton.

   

3) 

Hook up water line to toilet, fill tank, and test unit.

  8.2)  Installation of Toilet with ½” or ¾” (Use Floor Flange Extender Kit) Subflooring

  

1) 

Both wax toilet bowl gaskets are required.

   

2) 

Cut a 6½” diameter hole in the subfloor centered on the tank opening. 

   

3) 

Firmly press one of the wax toilet bowl gaskets into the plastic locator ring.

   

4) 

Place plastic locator ring on tank and firmly press into place until wax has completely filled the ring. This 

can be checked through the 4 air holes on the locator ring.

   

5) 

To complete installation, refer to the back of the toilet gasket carton for directions.

   

6) 

Hook up water line to toilet, fill tank, and test unit. 

Содержание QWIK JON 100

Страница 1: ...efects or other reproductive harm NOTICE TO INSTALLER Instructions must remain with installation SECTION 6 10 067 FM1469 0413 Supersedes 1209 P N 010536 PREINSTALLATION CHECKLIST 1 Inspect all materia...

Страница 2: ...Y AND ANY IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE AND OF MERCHANTABILITY SHALL BE LIMITED TO THE DURATION OF THE EXPRESSED WARRANTY Somestatesdonotallowlimitationsonthedurationofanimplied...

Страница 3: ...19 Meters 15 10 5 Feet 4 6 3 0 1 5 MODEL Liters 276 148 72 27 67 105 19 2 ft 5 9m 102 254 397 40 78 110 295 151 416 Gal Liters Gal Liters 17 5 ft 5 3m WM264 WM266 MODEL 102 MODEL 100 MODEL 101 PUMP P...

Страница 4: ...INSTALLATION OF THE CAST IRON SUPPORT Model 101 If the bolts are correct for your desired installation skip to STEP 6 NOTE If subflooring is being installed over the tank use the 20 X 3 long bolts sup...

Страница 5: ...in Figure 6 1 The pump should not turn ON 6 4 Fill the tank with an additional of water The pump should turn ON before the water level reaches 4 Refer to the Troubleshooting Guide on page 11 for prob...

Страница 6: ...RD SEAL NOTE INSTALL CORD SEAL BEFORE INSTALLING PIPE SEALS OVERLAP DETAIL TOP OF TANK GASKET AREA STEP 7 INSTALLATION OF LID AND ASSOCIATED PLUMBING NOTE STEPS 7 1 7 3 are for Models 100 102 only For...

Страница 7: ...K1589 Check local codes for discharge and vent sizing and installation Figure 9 1 NOTE The bottom of the additional fixture 3 diameter hole must be 5 or 6 minimum above the base of the tank depending...

Страница 8: ...BFLOOR 3 4 THICK MINIMUM 2X4 STUDS 2X6 FLOOR JOISTS VENT VENT GFCI DISCHARGE VENT 4 10 cm MIN NOTE 1 ALL VENTS AND DISCHARGE PIPING MUST BE INSTALLED ACCORDING TO LOCAL CODES 2 WALL BOARD REMOVED FOR...

Страница 9: ...OR 3 4 THICK MINIMUM 2X4 STUDS 2X6 FLOOR JOISTS VENT VENT GFCI 4 10 cm MIN NOTE 1 ALL VENTS AND DISCHARGE PIPING MUST BE INSTALLED ACCORDING TO LOCAL CODES 2 WALL BOARD REMOVED FOR CLARITY TO SHOW PIP...

Страница 10: ...ARGE PIPE TO ROOF VENT ACCORDING TO LOCAL CODES PIPING MUST BE INSTALLED NOTE ALL VENTS AND DISCHARGE 115V GROUND FAULT CIRCUIT INTERRUPTER GFCI DISCHARGE IF UNIT IS 230V THEN INSTALL GFCI 5 VERTICAL...

Страница 11: ...009119 Float Bulb 1 SK1587 MODELS 100 D 101 A 102 E 103 A REF NO DESCRIPTION QTY WM264 10 97 to Present WM211 07 01 to Present WM266 10 97 to Present WD266 11 99 TO Current WM270 10 95 to Current WD27...

Страница 12: ...terial has accumulated blocking flow of material Hold flush handle down on toilet for 15 seconds If unit will not clear unplug and wait 30 minutes Plug unit back in and repeat If unit still will not t...

Отзывы: