Zoeller ProPak AQUANOT Spin 508/53 Скачать руководство пользователя страница 5

5

MAINTENANCE

1. 

Inspect and test the system for proper operations at least every 3 

months.

 

(a) Red power on indicator light should be on indicating AC 

power is on.

 

(b)  Unplug primary pump and the control charger from power 

supply.

 

(c)  Fill  sump  with  water  to  the  “on”  level  for  the  DC  pump. 

Allow pump to run.

 

(d) The alarm will sound approximately 3 seconds after the 

pump starts to run.

 

(e)  Push alarm reset switch.  The alarm will go off.

 

(f)  Pump will shut off after water level is lowered and the float 

drops to the off position.

2.  Plug the control charger and the primary pump into the wall outlet.

 

(a)   The primary pump will come on and lower the water to the

 

 

 normal operating level and shut off.

 

(b)  The yellow charging light should be on.  The charger is 

replacing the energy consumed during the test.  The green 

light will come on after the charger has replaced the energy 

consumed during the test.

3.  Add distilled water to battery when necessary per battery 

manufacturer's instructions.  

CAUTION

 Battery acid is 

dangerous.  Take proper safety precautions.  Do not splash the 

acid.  

© Copyright 2020 Zoeller

®

 Co. All rights reserved.

TROUBLESHOOTING INFORMATION

1. 

DC Pump won’t run.

 

(a)  Check for proper connections.

 

(b)  Check all wire terminal points. Clean if required.

 

(c)  Check for low battery. Service battery if required.

 

(d)  Check 30 amp fuse on controller (see fig. 5). If fuse is blown, replace 

with 30 amp automotive blade fuse.

2. 

Pump runs but pumps very little or no water without AC power.

 

(a)   Check for low battery. Battery will recharge if green power “on” light 

indicates power has been restored and the float switch is in the off 

position.

 

(b)  If immediate usage is required, remove and replace dead battery with 

a full recharged battery.

 

(c)  Due to varying conditions, the pump may continue to run on a low battery 

without sufficient power to remove water.  Pump will not stop running 

until battery is below minimum voltage.

 (d) 

CAUTION

 Weak batteries can be recharged but may not store 

sufficient energy for full service. A weak recharged battery  can only 

be detected by reduced pumping time or by professional load testing 

equipment. If your emergency pump system is used frequently the 

battery should be checked by a qualified battery dealer.

3. 

Pump runs but pumps very little or no water.

 

(a)   Verfiy pump is connected completely.

 

(b)  Check to make sure pump weep hole is clear and unit is not airlocked.

 

(c)   Make sure discharge piping is not blocked.

4. 

Pump cycles too frequently.

 

(a)  Check positions of rubber stops on operational float rod.

 

(b)  Adjust upper rubber float stop as required. Recommended for standard 

installation.

5. 

Float switch in “on” position for more than 3 seconds. Pump won’t run.

 

(a)  Remove pump. Check for obstruction in pump preventing impeller from 

rotating.

6. 

Pump runs, but pumps water intermittently.

 

(a)  Pump is air locking. Check flow of water incoming to sump. If water is 

entering the sump at a high velocity creating a turbulent condition, a 

mixture of air and water may cause a complete or partial air lock and 

reduce or stop the flow of water in the discharge pipe.

 

(b)  Baffle the incoming stream of water to reduce turbulence. Diverting 

water stream against wall of basin usually corrects an air lock problem.

7.  Water level stays high. DC Pump continues to run.

 

   (a)  Battery is low.

     (b)  If power has been restored and water in sump remains high check 

primary pump. Service if required.

      (c)  After several hours the battery will be restored to full charge.

8.  Alarm sounds during battery recharge cycle.

     (a)  To silence alarm if alarm will not reset, unplug the charger from 115 V 

wall outlet, then disconnect the black lead from charger on negative (-) 

battery post. Check battery. Replace if necessary. Reconnect and refer 

to Installation (step 6).

Содержание ProPak AQUANOT Spin 508/53

Страница 1: ...a month Batteries contain acid and caution must be taken when handling 1 Check to be sure your power source is capable of handling the voltage requirements of the motor as indicated on the pump name plate 2 Vent hole It is necessary that all submersible sump effluent and sewage pumps capable of handling various sizes of solid waste be of the bottom intake design to reduce clogging and seal failure...

Страница 2: ...ouspecificlegalrightsandyoumayalsohaveother rights which vary from state to state In instances where property damages are incurred as a result of an alleged product failure the property owner must retain possession of the product for investigation purpose 1 Electrical wiring and protection must be in accordance with National Electrical Code and any other applicable state and local electrical requi...

Страница 3: ...ump pit too small D Pump will not shut off Debris under float assembly float bound by basin sides or other switch damaged or out of adjustment E Pump operates but delivers little or no water Check inlet strainer housing discharge pipe and vent holes for obstructions Discharge head exceeds pump capacity Low or incorrect voltage Incoming water containing air or causing air to enter pumping chamber I...

Страница 4: ...ended that the controller is plugged into a separate circuit different than the primary pump 4 Make certain the float switch clamp is tight on the pipe to avoid slippage Ensure that the off level of the float is 1 25 mm min above the discharge tee of the DC backup pump see Figure 1 Position pumps in the sump and move float up and down making sure of free movement without interference from any obst...

Страница 5: ...etorunonalowbattery without sufficient power to remove water Pump will not stop running until battery is below minimum voltage d CAUTION Weak batteries can be recharged but may not store sufficient energy for full service A weak recharged battery can only be detected by reduced pumping time or by professional load testing equipment If your emergency pump system is used frequently the battery shoul...

Страница 6: ...SENSOR OPTIONAL TYPICAL INSTALLATION EXPLODED VIEW OF PUMP SYSTEM SK3182 SK3223 FIGURE 2 FIGURE 1 1 1 2 SCH 40 PVC PIPE X 10 254 mm LG 1 1 2 SCH 40 PVC TEE NOTE CHECK VALVE SCREWS INTO PRIMARY PUMP DISCHARGE HAND TIGHTEN ONLY WEEP HOLE MUST BE VISIBLE OPERATIONAL FLOAT SWITCH DC PUMP CLAMP HIGH WATER REED SENSOR OPTIONAL CHECK VALVE O RING M53 PRIMARY PUMP CLAMP AQUANOT SPIN Copyright 2020 Zoeller...

Страница 7: ...ot limited to National Electrical Code local regional and or state plumbing codes etc Not intended for use in hazardous locations SK3185 FIGURE 3 Copyright 2020 Zoeller Co All rights reserved OPERATIONAL FLOAT SWITCH 30 AMP FUSE HI WATER REED SENSOR OPTIONAL BATTERY BOX DC PUMP 12 VOLT BATTERY SUPPLIED BY USER WHITE LEAD TO POSITIVE BLACK LEAD TO NEGATIVE CLAMP AQUANOT SPIN CONTROLLER FLOAT SWITCH...

Страница 8: ...ycle battery 175 minute reserve capacity or larger Do NOT use a maintenance free battery unless it is an AGM battery Replace your battery every 3 years Do not let corrosion build up on the battery terminals To check specific gravity follow the instructions on a hydrometer wet cell batteries only Use of the included plastic battery box is recommended to keep the battery safe and clean PROTECT YOUR ...

Отзывы: