WATER INLET AND OUTLET CONNECTIONS

CONNECTIONS TO HEAT PUMP

Plumb the ZHP-3216-TI, ZHP-80-TI and ZHP-65-TI heat pump inlet and outlet with schedule 40, 1.5 inch PVC.

MINIMUM/MAXIMUM WATER FLOW RATES

Your heat pump is designed to operate successfully between flow rates of  20 to 70 gallons per minute (GPM). The
plumbing system must be designed to maintain at least 20 GPM flow through the heat pump. At flow rates less than 20
GPM, the heat pump will not operate correctly and may become damaged. At flow rates above 70 GPM, the unit will
operate less efficiently and may become damaged.

A bypass valve (Fig. A) must be installed in order to isolate the heat pump.

We recommend installing a flow

meter between the bypass valve and the heat pump to determine the flow rate and properly adjust the position of the
bypass valve to the ideal range. A spring-check bypass valve is required when a pool pump of 2 HP or larger is used (for
bypass valve placement detail, see plumbing schematic below).

6

MODEL

MINIMUM

IDEAL

MAXIMUM

ZHP-3216-TI

30 GPM

35 GPM

70 GPM

ZHP-80-TI

30 GPM

35 GPM

70 GPM

ZHP-65-TI

20 GPM

35 GPM

70 GPM

ZHP-3216-TI

ZHP-80-TI
ZHP-65-Ti

Top View

CAUTION

Failure to establish proper water flow rates may result in damage to the heat pump and
void the warranty. Many flow meters require a long distance of straight tubing on the inlet
side to offer an adequate measurement.

!

Water Inlet

Water Outlet

Front View

Fig. A

Bypass valve           

 

DO NOT OVERTIGHTEN CONNECTIONS

DO NOT APPLY PRESSURE ON 

CONNECTIONS AND TUBING

WARNING

INLET

OUTLET

WINTERIZING HEAT EXCHANGER

GENERAL RECOMMANDATIONS

(CHECK OWNER’S MANUAL)

- TURN OFF THE UNIT

- SHUT OFF THE BREAKER ON THE HEAT PUMP

- UNCONNECT THE WATER INLET AND OUTLET 
  CONNECTIONS

- IF THE HEAT PUMP IS LEFT OUTSIDE DURING WINTER,
  PROTECT IT WITH A WATER PROOF COVER

CAUTION

Zodiac heat pumps are designed to work at a normal operating pressure of 20 PSI (1.4
bars). Maximum pressure is 30 PSI (2 bars). Heat pump installation must be designed to
insure that the maximum operating pressure is not exceeded; otherwise the warranty will
be void.

!

Flow meter

Bypass valve

Содержание ZHP-3216-TI

Страница 1: ...ZHP 3216 TI ZHP 80 TI ZHP 65 TI TITANIUM SERIES HEAT PUMPS USER S MANUAL INSTALLATION MANUAL W235611 rev 2 2005 2006...

Страница 2: ...se the equipment to gain access and be injured or drown WARNING Failure to heed the following warnings can result in permanent injury electrocution or drowning MANDATORY SAFETY INSTRUCTIONS Congratula...

Страница 3: ...Flow Rates Basic Connection Chlorinators Brominators and Other Automatic Systems Off Line Chlorinator or Brominator Salt Chlorinator Multiple Unit Connection IV Maintenance p 8 Cleaning Winterizing Ti...

Страница 4: ...ou will get that dollar multiplied by the COP factor back in total dollars worth of pool heat As an example the Zodiac ZHP 3216 TI with one of the higher COP s in the industry at 6 4 yields 6 40 worth...

Страница 5: ...g fan 4 feet 4 facing service panel 2 feet Objects should be placed as far as possible from where the air is discharged IMPORTANT Your heat pump must have sufficient clearance to properly function Oth...

Страница 6: ...nt detail see plumbing schematic below 6 MODEL MINIMUM IDEAL MAXIMUM ZHP 3216 TI 30 GPM 35 GPM 70 GPM ZHP 80 TI 30 GPM 35 GPM 70 GPM ZHP 65 TI 20 GPM 35 GPM 70 GPM ZHP 3216 TI ZHP 80 TI ZHP 65 Ti Top...

Страница 7: ...be installed as the last component on the pool return line the heat pump must be installed before the chlorinator or the warranty will be void Salt levels used with salt chlorinators will not harm ti...

Страница 8: ...ze the heat pump you must 1 Turn off the unit 2 Shut off the breaker of the heat pump electrical supply line 3 Disconnect the water inlet and outlet connections Figure A 4 Freely flush the condenser 5...

Страница 9: ...ity of the water to cause the degradation of metal is directly related to it Total alkalinity is the measure of the capacity of water to resist pH variation therefore it is also very important How to...

Страница 10: ...er acidity Acid water is often very clear because it is free of microorganisms but it can be unbalanced and become corrosive Sodium hypochlorite liquid chlorine Liquid chlorine is completely soluble i...

Страница 11: ...occurs when the selection label is no more shown on display SET In the MENU function it is used to set the selected parameter value and to enter the password In the STATUS function SET will be presse...

Страница 12: ...ualified electrician to take advantage of this feature Your installer will explain how the override works for your pool POWERED CARD Icon The POWERED CARD icon comes on when there is power to the unit...

Страница 13: ...w high pressure flow switch outputs are considered as enabled alarm start if contacts are open In case of alarm outputs will be controlled as shown in the following table LABEL Alarm description Reset...

Страница 14: ...recise its box is not and the thermometer may not be in line with the graduations written on the box In this condition the thermometer reads a temperature higher or lower than the real pool temperatur...

Страница 15: ...hours We will not be responsible for labor charges under this agreement if there were no defective parts Owner The warranty service agreement remains in effect as long as the product remains at the or...

Страница 16: ...on and adjustment of items such as evaporators condensers or air exchangers You must provide reasonable access to the unit s for servicing at all times Any work required to restore the property after...

Страница 17: ...ZODIAC POOL CARE INC 2028 N W 25th Avenue Pompano Beach FL 33069 1 800 830 4808 www zodiacpoolcare com CUSTOMER SERVICE info zodiacpoolheating com...

Отзывы: