2.3 I Operati ng
•
Check that there are no tools or other foreign objects in the machine.
•
The panel that provides access to the electrical enclosure must be properly secured in place.
•
Set the valves as follows: valve B wide open, valves A, C, D and E closed
: water inlet valve
: by-pass valve
: water outlet valve
: water inlet adjustment valve (opti onal)
: water outlet adjustment valve (opti onal)
• An incorrect by-pass setti ng may cause the heat pump to malfuncti on.
•
Ensure that the hydraulic connecti ons are enough ti ghtened and correctly so that there are no leaks.
•
Ensure that the device is fully stable.
•
Set the water circulati on running.
•
Close valve B gradually so that the fi lter pressure is increased by 150 mbars (0.150 bars).
•
Open valves A, C and D fully then valve E by half (the air which has built up in the heat pump condenser and the
fi ltrati on circuit will bleed out). If valves D and E are not present, open valve A wide and close valve C by half.
•
Connect the power supply to the heat pump.
• Press and hold
for 5 seconds to start the appliance in heati ng mode.
Aft er the start-up steps for your heat pump:
•
Shut down the water circulati on temporarily (by stopping the fi ltrati on or closing valve B or C) to check that you
device stops aft er a few seconds (via the acti vati on of the fl ow switch).
2.4 I Additi onal user functi ons
2.4.1 Adjusti ng the temperature setpoint (in heati ng mode)
The setpoint temperature is set by default to 28°C.
• Press
+
for 5 seconds:
then press
to confi rm,
•
Go to
then press
to confi rm,
•
Go to the
parameter, press
,
•
Go to
(= heati ng mode setpoint), press
,
•
Set the value you want with
or
, then press
to confi rm.
• Press
to exit.
The heat pump stops automati cally when the pool reaches the required temperature.
2.4.2 Sensor temperature reading
• Press
:
(water inlet sensor) then wait 3 seconds for the value to display.
• Press
:
(water outlet sensor) then wait 3 seconds for the value to display.
• Press
:
(air sensor) then wait 3 seconds for the value to display.
• Press
:
(low pressure sensor) then wait 3 seconds for the value to display.
• Press
to exit.