8
❸ Use
3.1 I Presentation of the regulation system
Ke
ys
Press and release
Press and hold
To confirm a value
"On/off"
To browse and adjust values
To quickly scroll through the values
Indic
at
or ligh
ts
Description
Steady
Flashing
Off
on
"On/Off"
indicator light
Appliance
switched
on
/
Inactive
reg
Heating indicator
lights
Appliance
currently
heating
On hold
Pool at
the desired
temperature
Water flow rate too low (less than 5 m³/h)
Filtration stopped
Set point temperature greater than pool water
temperature (the indicator flashes for 15
seconds then is lit steadily).
3.2 I Starting the appliance
•
Open all valves (V1, V2 and V3) (see §"2.2 I Hydraulic connections"),
•
Start the filter pump,
•
Gradually close the by-pass valve (V1),
•
Check that the water flow rate is between 5 and 30 m³/h. If the flow rate exceeds 30 m³/h, adjust valve 1
(V1) to reach 30 m³/h maximum,
• Check that there is no air in the circuit,
•
Connect the regulation system to the power supply and turn it on,
•
Adjust the set point temperature: to display and change the set point value, press
or
.
•
The temperature is regulated by degrees.
•
The set point can be adjusted to between 2°C and 40°C.
•
To check that the filtration time is long enough:
-
During the temperature rise phase, water circulation must be continuous (24 hours/day),
-
To maintain the temperature throughout the season, run "automatic" circulation for at least
12 hours/day (the longer this time, the more the operating range of the appliance will suffice
for heating).
3.3 I Checks to be carried out after operating for a few moments
The heater must stop operating when:
•
The temperature set point is lowered,
•
The regulation system stops,
•
Filtration stops.