ZMIO310 Vertical Bus Expansion Module User Manual V1.0
⚫
The fixed value is 2.
01h
CANFIG_1_INDENT
2
1 or 2
UNSIGND16
RW
⚫
In indicates the state after power off, resume initial state or keep state.
⚫
The usage of data value:
1.
After communication breaks, output states of DO/DOP module
and DA module recover initial values.
2.
After communication breaks, output states of DO/DOP module
and DA module keep current states.
02h
CONFIG_2_INDENT
0
0 or 5678 UNSIGND16
RW
⚫
Configure work mode
⚫
The usage of data value:
0: normal mode
5678: update mode.
⚫
Note: after entered update mode, if not to update, please power-on
again, it will exit automatically, this update mode is used to update
firmware of ECAT communication module.
(5001 +
expansion
submodule
address) h
00h
CONFIG_DATA
2
2
UNSIGND8
RO
⚫
The number of default subindex, the fixed value is 2.
⚫
Expansion submodule address: the nearest expansion submodule
address to coupler is 0, addresses of following other modules
accumulate in order, namely, 0, 1, 2, 3…
01h
CONFIG_1_INDENT
2
2~7 or
10~15
UNSIGND16
RW