VENTILATION
This appliance is only intended to be fully fitted in a kitchen.
• This appliance is not designed to be used as a tabletop appliance or inside a
cupboard.
• The fitted cabinet must not have a back wall behind the appliance.
• A gap of at least 1 49/64” must be maintained between the wall and the base
or back panel of the unit above.
• The fitted cabinet must have a ventilation opening of 38 3/4 in² on the front. To
achieve this, cut back the base panel or fit a ventilation grill.
• Ventilation slots and intakes must not be covered.
• The safe operation of this appliance can only be guaranteed if it has been
installed in accordance with these installation instructions.
• The units into which the appliance is fitted must be heat-resistant up 194°F.
• Note: There should be a gap above the oven.
INSTALLATION
Cabinet R
equir
ements
Flush installation also requires:
• Two side cleats to be attached inside the cabinet frame, recessed from the front
• A 5/16” baseplate underneath the unit body.
INSTALLATION
MWO-24
MWO-30
MWO-24
MWO-30