InBio Pro Series Access Control Panels INSTALLATION guIDE
Switching Dry Contact to Wet Contact
Important Notes:
The factory default jumper setting is set as dry mode. If you want to power the
lock from the panel, you must take the following steps:
1.
Take apart the cover of InBio460Pro. Push the tab inward (see fi gure 21)
2.
Select the appropriate lock relay and fi nd its jumpers
3.
Take off the jumpers and change
to
4.
Connect the lock as show in the diagram, (see fi gure 23 and 24)
Back of InBio460Pro
Select one Relay
Default setting
1, 2 - 3, 4
Take off jumpers
Jumpers
Plug Jumpers
2, 3 - 4, 5
Figure 22
Figure 21