background image

Ziton Wireless Manual Call Point Installation Guide

General

The Ziton wireless manual call point is available under 

the following part number:

PART NO   

VARIANT TYPE

ZPR485-3   

Ziton wireless manual call point

The address of the unit is set when programming the 

device to the system (see commissioning manual for 

details). The installation must conform to BS5839:Part 1 

(or applicable local codes). 

Installation of Ziton wireless manual call point

Remove the back plate fixing screw. Retain this for future 

use. Insert flat bladed instrument into the removal slot 

and remove the back plate from the transmitter/battery 

section. (See Figure 1).

Mount the back box 1.4m from the floor, using suitable 

fixings and fasteners. A minimum of two mounting holes 

must be used. Countersunk head screws must be used to 

avoid the possibility of damage to the internal 

components. (See Figure 2).

© 2015 EMS Security Group Ltd. All rights reserved

1 / 4

4 / 4

MK106 Iss7 24/07/15 AJM

© 2015 EMS Security Group Ltd. All rights reserved

Figure 1

Power jumper

Figure 2

Figure 3

Wall mounting positions

To ensure correct operation, connect the power jumper 

across the PIN header on the battery PCB located on the 

rear of the call point as shown in Figure 3. 

Specification

Operating 
Temperature
 

-10 to +70°C (ambient)

Storage 
Temperature
 

0 to +35°C

Humidity  

Up to 95% non-condensing

Supply  

6x AA Alkaline (Panasonic LR6AD  

 

 

Powerline / Varta 4006 Industrial) 

IP Rating   IP24

Operating 
Frequencies
 

868 MHz

Output Transmitter
Power
 

 

Variable 0-14 dBm

Dimensions 

89mm (W) 92mm (H) 70mm (D)

Weight   0.40kg

Regulatory information

Manufacturer 

EMS Security Group Ltd.  

 

 

 

Technology House, Sea Street,    

 

 

Herne Bay, Kent, CT6 8JZ, 

  United 

Kingdom

Year of
manufacture
 

See serial number on unit

Certification

Certification body 

CPD Certificate
DOP
  

0359-CPR-0168

Approved to 

EN54-11

  EN54-25

Application 

Intended for use in fire detection

 

 

and fire alarm systems in and

 

 

around buildings. Indoor use only.

European Union

directives  

EMS Security Group Ltd hereby    

 

 

declares that this device is in

 

 

compliance with the essential    

 

 

requirements and other relevant

 

 

provisions of Directive 2014/53/EU  

  (R&TTE 

directive).  

 

 

2012/19/EU (WEEE directive):

 

 

Products marked with this symbol  

 

 

cannot be disposed of as unsorted  

 

 

municipal waste in the  European  

 

 

Union. For proper recycling, return  

 

 

this product to your local supplier  

 

 

upon purchase of equivalent new  

 

 

equipment, or dispose of it at

 

 

designated collection points. 

 

 

For more information see

  www.recyclethis.info

 

 

Dispose of your batteries in an    

 

 

environmentally friendly manner  

 

 

according to your local regulations.

Contact information

For contact information, see ww.utcfireandsecurity.com
 

MK106 Iss7 24/07/15 AJM

12