6.4. Exiting Alignment Mode.
Do not remove the detector from the wall during this action.
Using the mode switch (See fig. 4) select ‘Operating Mode’ (Switch will be in the down position).
On exiting ‘Alignment mode’ the Detector will perform an internal calibration check. If this fails, which would be
due to bad alignment or either electrical or optical noise, the power level will try to compensate. If, after 60
seconds, the power level is still not correct, the Fault LED will flash every 2 seconds and the panel will show a
Fault. In this case the alignment procedure must be repeated.
7. System Testing.
After successful installation and alignment the System will require testing for both alarm and fault conditions.
7.1. Alarm (smoke) Test.
Taking note of the threshold selected during installation (default 35%).
Select obscuration mark on filter to correspond with the Detector alarm threshold (see fig. 3).
Place the filter over the receiver optics (Top of Detector Head
−
opposite end to the status indication LED’s) at
the correct obscuration value determined by the threshold selected, i.e. if a threshold of 35% has been selected
position the filter just past the 35% obscuration value on the filter (see fig 3.).
Take care not to cover the transmitter optics.
The Detector will indicate a fire within 10 seconds.
7.2. Fault Test.
Cover the Prism(s) totally with a non-reflective material and confirm that the Detector indicates a fault condition
after approximately 10 seconds. The Amber LED on the Detector will flash, and the panel will show a Fault
condition. The fault condition will automatically reset after a period of 10 seconds when the obstruction is
removed.
Fig. 3.
Í
obscuration value
Align filter for correct obscuration/threshold setting
Transmitter Optics
Receiver Optics
Status Indication LED’s
RED
AMBER