10. Address Settings. 

 
 

Table 1 - Address settings: 

 

Address 

 # 

Switch  

Configuration 

Address

Switch  

Configuration  

Address

Switch 

Configuration  

 

SW1           SW8

 

SW1           SW8

 

SW1          SW8 

0 Not 

allowed   

 

 

 

1  1000000X 44 0011010X 87 1110101X 
2  0100000X 45 1011010X 88 0001101X 
3  1100000X 46 0111010X 89 1001101X 
4  0010000X 47 1111010X 90 0101101X 
5  1010000X 48 0000110X 91 1101101X 
6  0110000X 49 1000110X 92 0011101X 
7  1110000X 50 0100110X 93 1011101X 
8  0001000X 51 1100110X 94 0111101X 
9  1001000X 52 0010110X 95 1111101X 

10 0101000X 53 1010110X 96 0000011X 
11 1101000X 54 0110110X 97 1000011X 
12 0011000X 55 1110110X 98 0100011X 
13 1011000X 56 0001110X 99 1100011X 
14 0111000X 57 1001110X 100 0010011X 
15 1111000X 58 0101110X 101 1010011X 
16 0000100X 59 1101110X 102 0110011X 
17 1000100X 60 0011110X 103 1110011X 
18 0100100X 61 1011110X 104 0001011X 
19 1100100X 62 0111110X 105 1001011X 
20 0010100X 63 1111110X 106 0101011X 
21 1010100X 64 0000001X 107 1101011X 
22 0110100X 65 1000001X 108 0011011X 
23 1110100X 66 0100001X 109 1011011X 
24 0001100X 67 1100001X 110 0111011X 
25 1001100X 68 0010001X 111 1111011X 
26 0101100X 69 1010001X 112 0000111X 
27 1101100X 70 0110001X 113 1000111X 
28 0011100X 71 1110001X 114 0100111X 
29 1011100X 72 0001001X 115 1100111X 
30 0111100X 73 1001001X 116 0010111X 
31 1111100X 74 0101001X 117 1010111X 
32 0000010X 75 1101001X 118 0110111X 
33 1000010X 76 0011001X 119 1110111X 
34 0100010X 77 1011001X 120 0001111X 
35 1100010X 78 0111001X 121 

Not 

allowed 

36 0010010X 79 1111001X 122 

Not 

allowed

 

37 1010010X 80 0000101X 123 

Not 

allowed

 

38 0110010X 81 1000101X 124 

Not 

allowed

 

39 1110010X 82 0100101X 125 

Not 

allowed

 

40 0001010X 83 1100101X 126 

Not 

allowed

 

41 1001010X 84 0010101X 127 

Not 

allowed

 

42 0101010X 85 1010101X 

‘ON’  Type 

43 1100010X 86 0110101X 

‘OFF’

Type 

 

 

  

 

 

 

 
 
 
 

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание ZP7BMR-100

Страница 1: ...Range 50 100 Metres Unique simple alignment Loop powered Selectable alarm thresholds Low current consumption Automatic contamination compensation ZITON ZP7BMR 50 100 Loop Powered Analogue Addressable...

Страница 2: ...ism Targeting page 5 6 Alignment page 5 to 7 7 System Testing page 7 8 Connection and configuration Settings page 8 9 Detector Back View page 9 10 Address settings page 10 11 Clearances page 11 12 Tec...

Страница 3: ...ondition being rectified The Detector monitors long term degradation of signal strength caused by component ageing or build up of dirt on optical surfaces This operates by comparing the received infra...

Страница 4: ...creased from 7 5 metres either side of the beam to 7 5 7 5 x 20 100 metres 9 metres Therefore with a roof pitch of 20 degrees the lateral coverage can be increased from 7 5 metres either side of the b...

Страница 5: ...ON OFF ON OFF ON X Logic 1 0 1 0 1 0 1 X The Detector Head Assembly is now ready for installation If configuration switches 3 and 4 require resetting after installation a power down reset is required...

Страница 6: ...horizontal and vertical thumbwheels until the Amber LED is flashing Both the Red and Amber LED will be OFF when no signal is being received The Red LED will start to flash when a weak signal is receiv...

Страница 7: ...be receiving a fringe reflection from another object FLICKERING RED AMBER This state can occur sometimes It means that the infrared power is stepping through the optimum setting for the current orient...

Страница 8: ...n filter to correspond with the Detector alarm threshold see fig 3 Place the filter over the receiver optics Top of Detector Head opposite end to the status indication LED s at the correct obscuration...

Страница 9: ...itch with the following features The address settings is set up via the 8 way DIP switch on the lower part of the beam See Fig 4 8 3 Typical Loop Wiring Fire Panel Connections Loop Output Input to Nex...

Страница 10: ...9 Detector Interface Assembly Configuration Settings DIP SWITCH SETTINGS X X X X X X X X X X X X X X X X X X X 2 X 1 3 4 Fig 4 www acornfiresecurity com www acornfiresecurity com...

Страница 11: ...0001011X 19 1100100X 62 0111110X 105 1001011X 20 0010100X 63 1111110X 106 0101011X 21 1010100X 64 0000001X 107 1101011X 22 0110100X 65 1000001X 108 0011011X 23 1110100X 66 0100001X 109 1011011X 24 000...

Страница 12: ...ameter clearance down the entire beam path If there are highly reflective objects within 1 metre diameter of the beam path for the first 20 metres of the beam path for the ZP7BMR 100R then tests shoul...

Страница 13: ...rt 5 use 25 and 35 default thresholds The threshold of 50 is recommended for hostile and extreme environments When in normal run mode the fire panel controls the Red LED flashing Amber LED flashing on...

Отзывы: