Installation Sheet 

No.: 1774 iss 03 

ZP755R-2 Addressable Room Sounder 

Installation sheet 

501-1774ZE-1-03 

ZP755R-2 Addressable Room Sounder 

Page 4 

14/11/2006 

 

Figure 4 

 

Number of Sounders per Loop

 

See Figure 5. 

The ZP755R-2 sounder can be powered directly from 
the loop of a ZP5 or ZP3 panel. The table below, read 
in  conjunction  with  figure  5,  gives  the  quantity  of 
detectors  and  sounders  that  can  be  connected  to  a 
2-core screened loop of: 

1000 metres cable size 1.5 mm

1. 

10 metres panel to devices 

50 detectors and 50 sounders 
63 detectors and 42 sounders 

2. 

100 metres panel to devices 

45 detectors and 45 sounders 
63 detectors and 40 sounders 

3. 

200 metres panel to devices 

40 detectors and 40 sounders 
63 detectors and 37 sounders 

4. 

300 metres panel to devices 

37 detectors and 37 sounders 
63 detectors and 35 sounders 

 

Figure 5 

 

 

 