Chapter 1: Maintenance 

 

ZP3-ECU Extinguishing Control Unit Maintenance Manual 

Preventive maintenance 

Preventive maintenance is divided into the following categories: 
•  Daily checks 
•  Weekly maintenance 
•  Quarterly maintenance 
The daily and weekly maintenance tasks require no technical expertise and 

should be carried out by the panel operator. 

Daily 

The ECU must remain clean at all times. Perform the following: 
•  Clean the outer surface of the unit to remove any excess dust using a damp 

cloth. 

•  Check for correct and smooth operation of the key switches. Lubricate sticky 

key switches if required using 2 or 3 drops of a general purpose lubricant (for 

example 3 in 1 oil). 

Weekly 

•  Check any reports sent from the ECU to the fire alarm control panel. Under 

normal conditions no abnormal reports should be detected. 

•  Check the front panel of the ECU and any status units. Only the POWER ON 

and Automatic/Manual LEDs should be illuminated. 

•  Test the function of the Automatic/Manual key switch by operating the switch. 

Check that the printer (if available) on the fire alarm control panel indicates 

the change in switch position. 

•  Restore the system to previous configuration. 
•  Log the test in the system log. 

Quarterly maintenance 

Quarterly maintenance must be carried out by suitably trained personnel. Such 

personnel may be direct employees of the company, or may be contracted from 

the maintenance company responsible for servicing. 
Quarterly maintenance is designed to pre-empt any problems that may arise and 

to check that the system is functioning to its installation specifications. The 

services should be arranged through a maintenance contract with a servicing 

company. This agreement should specify how to contact the service company 

and how they can access the premises. 
Repair services should be available within 24 hours. For premises in continuous 

use, an engineer should be on call at all times. The servicing company should 

have engineers trained in servicing Ziton equipment. The owner of the fire alarm 

system is responsible for ensuring that the company contracted is competent to 

carry out the work. 

Содержание ZP3-ECU

Страница 1: ...ZP3 ECU Extinguishing Control Unit Maintenance Manual P N 503 0800ZE M 04 ISS 31JUL23...

Страница 2: ...rked with this symbol cannot be disposed of as unsorted municipal waste in the European Union For proper recycling return this product to your local supplier upon the purchase of equivalent new equipm...

Страница 3: ...ce Manual i Content Important information ii Limitations iv Chapter 1 Maintenance 1 Summary 2 Notification and preparation 4 Preventive maintenance 5 Fault finding 7 Chapter 2 Fault finding communicat...

Страница 4: ...under any theory of liability whether based in contract tort negligence product liability or otherwise Because some jurisdictions do not allow the exclusion or limitation of liability for consequenti...

Страница 5: ...com policy product warning or scan the QR code Advisory messages Advisory messages alert you to conditions or practices that can cause unwanted results The advisory messages used in this document are...

Страница 6: ...s between fire detection and extinguishant release plus deliberate delays to allow for personnel evacuation Maintenance faults As with most extinguishing systems the most common cause of their malfunc...

Страница 7: ...hing Control Unit Maintenance Manual 1 Chapter 1 Maintenance Summary This chapter provides maintenance information for the ECU Content Summary 2 Notification and preparation 4 Preventive maintenance 5...

Страница 8: ...ng condition at all times This involves arranging for the system to be checked tested and serviced as described in this manual The maintenance procedures described are recommendations There may be add...

Страница 9: ...are used Type of extinguishing cylinders equipment and extinguishant details Physical layout of loops and devices The type and the address applicable to each extinguishing control unit should be recor...

Страница 10: ...d their locations should be recorded Any actions taken should also be recorded Dates times and types of all defects and faults and the corrective actions taken Dates times and types of all tests under...

Страница 11: ...he Automatic Manual key switch by operating the switch Check that the printer if available on the fire alarm control panel indicates the change in switch position Restore the system to previous config...

Страница 12: ...the status unit Check that the bell output responds accordingly 7 Activate the second input mapped to activate the ECU using canned smoke to activate a smoke detector if required 8 Check after the del...

Страница 13: ...rom the extinguisher cylinder if applicable Fault finding Faults that occur on the ECU or in building wiring are reported by the fire alarm control panel The Fault LED on the ECU front panel illuminat...

Страница 14: ...Chapter 1 Maintenance 8 ZP3 ECU Extinguishing Control Unit Maintenance Manual...

Страница 15: ...fire alarm control panel Note Fault messages on the fire alarm control panel display depend on the control panel used The examples included in this chapter are for the ZP3 Fire Alarm Control Panel Fo...

Страница 16: ...Never use a megger or any other high voltage instrument on detection or alarm lines while there are any devices connected to them This causes irreparable damage to the devices Never replace a panel PC...

Страница 17: ...terminals An ECU that is out of calibration or is faulty Interference on the loop to which the device is attached Corrective actions 1 Press the Accept Panel Silence button to silence the buzzer and...

Страница 18: ...Dev 001 Event 001 Second Floor Laundry Room RELAY FAULT Zone 001 Dev 086 Event 002 The event is printed if a printer is configured Zone in which the relay fault occurred is indicated by the appropriat...

Страница 19: ...n the display for example TYPE FAULT Zone 001 Dev 001 Event 001 Second Floor Laundry Room The event is printed if a printer is configured Possible causes Device addresses have been swapped within the...

Страница 20: ...is printed if a printer is configured Possible causes An isolator on the loop has caused the device to open circuit Field wiring is disconnected or there is an open circuit Corrective actions 1 Press...

Страница 21: ...ay depend on the control panel used The examples included in this chapter are for the ZP3 Fire Alarm Control Panel For other control panels refer to the documentation for the control panel Content ECU...

Страница 22: ...Indicated current ratings are dependant upon the capacity of the power supply unit Figure 1 ECU main board fault LEDs 1 Extinguishant Pressure Low LED 2 Fire Bell Fault LED 3 Detonator Fault LED ensu...

Страница 23: ...inted if a printer is configured The appropriate red Zone LED illuminates to indicate the zone in which the fault occurred Possible causes A fault on the control system falls into one of the following...

Страница 24: ...the ECU or status unit display PCB respectively is not correctly setup or the monitored circuit has gone open circuit Corrective actions 1 Press the Accept Panel Silence button to silence the buzzer a...

Страница 25: ...P3 Fire Alarm Control Panel also illuminates GNFLT Zone 001 Dev 5001 Event 002 Possible causes The EOL resistor across the actuator switch is not inserted or the circuit is an open circuit The detonat...

Страница 26: ...panel and the panel buzzer sounds The Fault LED on the fire alarm control panel also illuminates GNFLT Zone 001 Dev 5001 Event 002 Possible causes The EOL resistor across the Extinguishant Pressure L...

Страница 27: ...he Fault LED on the fire alarm control panel also illuminates GNFLT Zone 001 Dev 5001 Event 002 Possible causes The EOL resistor across the fire bell is not inserted or the monitored circuit wiring is...

Страница 28: ...e Fault LED on the fire alarm control panel also illuminates GNFLT Zone 001 Dev 5001 Event 002 Possible causes The EOL resistor across the extinguishant discharge siren is not inserted Monitored wirin...

Страница 29: ...lso illuminates GNFLT Zone 001 Dev 5001 Event 002 Possible causes 1 SWT3 1 on the main PCB of the ECU is set to ON and the Extinguishant Pressure Verification Switch is NOT connected 2 SWT3 1 on the m...

Страница 30: ...one 001 Dev 5001 Event 002 Possible causes Total loss of power to the ECU Loss of power to a section of the ECU main board Corrective actions 1 Press the Accept Panel Silence button to silence the buz...

Страница 31: ...eration of controls on the status unit does not evoke appropriate response on the ECU Possible causes The wiring connections to the status unit are open circuit or incorrect The ribbon cable connected...

Страница 32: ......

Отзывы: