Public level operation
Public level operations are those that can be performed by any user. No
password is required to perform tasks at this level.
This user level lets you:
• Silence the buzzer
• Cancel an active sounder, fire routing, or fire protection delay
• View current events
• View support information
Silencing the buzzer
To silence the control panel buzzer, press the Panel Silence button. A steady
Panel Silence LED indicates that the buzzer was silenced.
Note:
Depending on the control panel configuration, the buzzer may re-sound for
each new event reported.
Cancelling an active sounder delay
If a sounder delay is enabled and active (counting down), press the Sounder
Delay button to cancel the delay and activate sounders immediately.
A sounder delay is indicated as follows:
• A steady Sounder Delay LED indicates that a delay is enabled
• A flashing Sounder Delay LED during a fire alarm indicates that the
configured delay is active (sounders are activated when the configured delay
elapses or when the delay is cancelled)
A fire alarm activated by a manual call point overrides any configured delay and
activates the sounders immediately.
Cancelling an active fire routing or fire protection delay
If a fire routing or fire protection delay is enabled and active (counting down),
press the corresponding ON/Acknowledged or Delay button to cancel the delay
and activate the feature immediately.
Fire routing and fire protection delay indications are shown in the table below.
Table 6: Fire routing and fire protection delay indications
Delay type
Delay indications
Fire routing
A steady Fire Routing Delay LED indicates that a delay is enabled.
A flashing Fire Routing Delay LED during a fire alarm indicates that the
configured delay is active (fire routing is activated when the configured delay
elapses or when the delay is cancelled).
Fire protection
A steady Fire Protection Delay LED indicates that a delay is enabled.
A flashing Fire Protection Delay LED during a fire alarm indicates that the
configured delay is active (fire protection is activated when the configured
delay elapses or when the delay is cancelled).
16
ZP2-F Series Fire Alarm Control Panel Operation Manual