Chapter 1: Overview
ZP3 Fire Alarm Control Panel Installation Manual
23
6. Ensure that the earth connections are made as shown in Figure 20 on page
22.
Caution:
Do not overtighten the panel clamp screws. Failure to comply will
damage the unit.
7. Secure the mounting bracket to the panel printer using the screws provided.
8. Connect the external circuit board (attached to the mounting bracket) to the
printer using the orange and black cable.
9. Connect the display board and the printer board to the printer using the ribbon
cable provided, as shown in Figure 20 on page 22.
10. Connect 24 VDC power to the printer using the black and red power lead.
11. Power up the panel and configure the printer on the panel.
Once installed the printer must be configured to operate as required. It can be
programmed to print or suppress different types of messages (e.g. print fire
alarms message, suppress disabled messages, etc.). This programming is done
in the panel Setup menu. See “System Configuration > Printer” on page 79 for
details.