background image

Mounting instructions

In order to minimise the installation time, it is strongly recommended, that

the following procedure is followed:

1

Remove plastic fascia by removing the two screws from the top

plastic cover.

2

Disconnect the two secondary transformer wires from the terminals

marked ‘AC~’ on the PCB. These are located on the right-hand side

of the fire panel.

3

Remove the two screws that hold the bottom plastic cover in place,

then lift away from fire panel housing. Store cover assembly in a safe

place to prevent damage during initial installation.

NOTE: DO NOT REMOVE THE PCB FROM THE PLASTIC

MOULDING.

4

Using the back box as a Drill template, mark through fixing positions,

prepare the fixing holes, and fit onto wall using an appropriate

mounting system.

Ensure the back box is not contaminated with drilling debris, e.g.

brick dust, as this can adversely affect the electronic circuitry.

5

Prepare cable entries via the 20mm knockouts provided in the top

and rear of back box using appropriate glanding system.

6

Remove any debris from the back box.

Wiring mains and battery

1

Configure the Auxiliary relay link for fire or fault operation. The

factory default setting is activation on fault.

2

Connect mains wiring to terminal block in the back box as marked.

NOTE: AN EARTH CONNECTION MUST BE MADE TO THE

TERMINAL BLOCK AS MARKED.

3

With the mains supply isolated, replace the lower plastic cover

assembly containing the PCB. Ensure the battery wires are routed to

the top left-hand side of the back box and the transformer secondary

wires are routed towards the right hand side. The PCB locating holes

should engage on the metal mounting tabs.

4

Reconnect the transformer secondary wires to the PCB terminals

marked ‘AC’.

Note: Polarisation of this connection is unimportant

5

Fit and tighten the two securing screws that hold the PCB moulding

in place. Ensure that the moulding has properly engaged at the

bottom of the metal back box. Do not over tighten two retaining

screws.

6

Fit battery into left-hand side of the back box and connect battery

using leads supplied. Ensure correct polarity is always observed.

The panel is now active and will indicate a ‘POWER FAULT’ and

“GENERAL FAULT” until the mains supply is re-instated, and

the panel ‘RESET’.

7

Instate the mains supply, enter access code then press the ‘RESET’

button, see operating instructions.

8

Check panel is operating normally. The panel should only show the

green “POWER ON” indicator.

9

You have now proved that the panel is free of faults.

2

61640610 issue 6_8/02

1 & 2 zone - Fire alarm panels

Battery

leads

System

fuses

Transformer

AC low volts

input

Locating points

for enclosure tabs

(In two positions)

8K2

E.O.L

resistors

125mA

1A

315mA

315mA

1.6A

Lower PCB cover

Figure 2

Terminals and

fuses

View on back of pcb

(Some components not shown for clarity)

Battery

leads

Locating

points for

enclosure

tabs

(In two positions)

PCB

Sounder

FAULT/FIRE

AUXILIARY RELAY

(Shown in default “FAULT” position)

black

red

Figure 3 Setting the auxiliary relay operation

PCB TERMINAL

BLOCKS

BATTERY

CABLE ENTRY

POINTS TOP AND REAR

METAL

HOUSING

SECONDARY

TRANSFORMER

WIRES

TOP

COVER

FIXING

POINTS

BOTTOM

COVER

FIXING

POINTS

Figure 1 Panel with top cover removed

Содержание ZIRCONLC1

Страница 1: ...gured as a fault relay as standard EN54 requirement however the relay can be configured as an auxiliary fire relay by moving a jumper link from the fault position to the fire position on the back of t...

Страница 2: ...back box and the transformer secondary wires are routed towards the right hand side The PCB locating holes should engage on the metal mounting tabs 4 Reconnect the transformer secondary wires to the P...

Страница 3: ...mains supply enter access code then press the RESET button 8 Refit plastic fascia Do not over tighten two retaining screws 61640610 issue 6_8 02 3 1 2 zone Fire alarm panels END OF LINE RESISTOR 8K2 O...

Страница 4: ...and then automatically reset 1 Enter the access code to get into supervisor mode if not already entered 2 Hold down the ADVANCE push button for at least 2 seconds until you hear a double bleep 3 The...

Страница 5: ...ress reset to exit supervisor mode Note Pressing reset whilst the sounders are disabled will not revert the panel to normal operation 61640610 issue 6_8 02 5 1 2 zone Fire alarm panels Sounder General...

Страница 6: ..._________________________ Site address___________________________________________________________________________ ______________________________________________________________________________________...

Страница 7: ...61640610 issue 6_8 02 7 1 2 zone Fire alarm panels Fire panel event record Date Weekly Qtly Event Action Required Completed Name...

Страница 8: ...8 61640610 issue 6_8 02 1 2 zone Fire alarm panels Date Weekly Qtly Event Action Required Completed Name...

Отзывы: