AC Switch Delay
The switching time from power failure to switch-over to Inverter/Controller power can be set by the user. The range is from
about 6 msecs to 200 msecs. The default is 6 msecs, which is the fastest time. The user may want to extend the time if they have
some equipment that might be upset by the fastest switching times. You might want some equipment to completely power
down during a power failure.
The 00 ms time represents 6 msec. The time can be set in 8 msec steps.
To set the delay time, move the cursor to
“SET”
and Press
“ENTER”
.
Use the UP and Down keys to adjust the value and press
“ENTER”.
Ethernet Communications
The Ethernet Display shows the IP address and the MAC Address for the Ethernet Board. There is nothing to change or adjust on
this display.
AC Switch Display
Ethernet Communications Display
25
/
UPSTEALTH®
USER MANUAL