INSTRUCTIONS FOR INSTALLATION AND OPERATION OF ZILMET USA EXPANSION TANKS 

PROFESSIONAL INSTALLATION REQUIRED 

rev. 

Sep2020

 

page 

4

 / 7

 

INSTALLATION IN PUMP SYSTEMS FOR STORAGE AND LIFTING OF POTABLE WATER

 

After the back-flow preventer at the exit of the pump, as shown in the picture. 

A = Manometer 

B = Backflow preventer 

C = Globe valve 

D = Pressure switch 

E = Safety valve 

F = Basin with submerged pump/ 

G = Switch board 

H = Water system 

I = Interchangeable membrane pressure tank 

Note: pre-charge of the tank must be set 3 psi lower than the minimum pressure switch setting at which the pump starts. 

INSTALLATION IN SOLAR SYSTEMS 

For  installation  and  operation  review  the  system  norms.  Solar  vessel  must  be  installed  in  the  supply  line  of  the  solar  collector  through  use  of  a 

suitable temperature-resistant solar ball valve with a shut off to the system.  The maximum working temperature in the membrane may not exceed 

212 °F. This can be achieved by installing a temperature control system or using a vessel for compensating temperatures (type ZILMET VSG). The 

solar  vessel  must  be  installed  in  frost-free  areas  and  have  no  direct  heat.  During  the  start-up,  the  pre-charge  of  the  vessel  must  be  adjusted 

according to the system data and must be written on the label. When checking the systems pressure, the maximum working pressure of the solar 

vessel must be considered and, if necessary, the solar vessel must be separated from the system. The solar vessel is resistant to 70% antifreeze. 

The use of proper anti-scale and corrosion inhibitors additives is required in solar systems.

 

Do not insulate the connecting pipe or the solar expansion vessel. 

Beware: this can get hot

. Therefore, precautions should be taken 

to ensure that access to this equipment is restricted. Do not install 

where children are present or may be present. 

Maintenance notes for solar vessels

 

When solar expansion vessel is connected to the system using a 

butterfly  solar  valve,  please  follow  these  instructions  before 

performing gas pre-charge checks: 1) close the knob and open the 

drain  nipple  to  completely  drain  the  tank,  then  check  the  pre-

charge pressure; 2) after checking the pre-charge pressure, close 

the  drain  nipple  and  open  the  knob. 

When  opening  the  drain 

nipple  of  the  butterfly  valve  to  drain  the  solar  expansion 

vessel,  please  note  that  the  solar  fluid  coming  out  from  the 

butterfly  valve  may  be  hot:  therefore  precautions  must  be 

taken to avoid property damage, scalding and/or bodily injury.

 

When rinsing the solar system, the solar vessel must be separated 

from the system by closing the ball valve outlet, thereby preventing 

dirt  particles  from  entering  the  solar  vessel.  Dirt  particles  may 

cause damage to the membrane or corrosion. 

Pay  particular  attention  to  the  fact  that  the  solar  fluids  may 

undergo to chemical degradation (pH lowering) due to thermal 

effect, causing corrosion of the tank and of other parts of the 

system

.  This  may  happen  also  when  the  system  is  not  working, 

due to the stagnation of the fluid in the solar panels. The personnel 

in  charge  of  installation,  commissioning  and  maintenance  must 

take into account this possibility and must follow the instructions of 

the  supplier  of  the  solar  fluid  regarding  periodical  substitution  of 

the fluid itself and/or adding proper additives to the system. 