TR250
12410-0701-03
Page
15 / 18
www.ziehl.de
12
Technical Data
Rated supply voltage Us:
AC/DC 24
– 240 V
Tolerance
DC 20, 4 - 297 V AC 20 - 264 V 50/60 Hz
Power consumption
< 3 W
< 7 VA
Relay output:
3 x co (change-over)
Switching voltage
max. AC 415 V
Switching current
max. 5 A
Switching power
max. 1250 VA (resistive load)
max. 120 W at DC 24 V
UL electrical ratings:
250 V ac, 5 A, resistive
E214025
240 V ac, 1/2 hp
120 V ac, ¼ hp
B 300
– pilot duty, UL 508
Rated operational current Ie:
AC15
Ie = 3 A
Ue = 250 V
DC13
Ie = 2 A
Ue = 24 V
Ie = 0,2 A
Ue = 125 V
Ie = 0,1 A
Ue = 250 V
Recommended fuse for contacts
T 3,15 A (gL)
Expected contact life mechanical
3 x 10
7
operations
Expected contact life electrical
1 x 10
5
operations with AC 250 V / 6 A
Test conditions
EN 61010-1
Rated impulse voltage
4000 V
Overvoltage category
III
Contamination level
2
Rated insulation voltage Ui
300 V
On-time
100 %
EMC-tests
EN 61326-1
emitted interference
EN 61000-6-3
Burst
EN 61000-4-4 +/-4 kV
Pulse 5/50 ns, f = 5 kHz, t = 15 ms, T = 300 ms
SURGE
IEC 61000-4-5 +/-4 kV
Impulse 1,2/50 µs (8/20 µs)
discharge of static electricity
IEC 61000-4-2 +/-4 kV contact,
+/- 8kV air
Environmental conditions
Ambient temperature range
-20 °C ... +65 °C
Storage temperature range
-
20 °C … +70 °C
Altitude
Up to 2000 m
Climatic conditions
5
– 85 % rel. humidity, no condensation
External wiring temperature range
-
5 °C … +70 °C
Vibration resistance EN 60068-2-6
2…25 Hz ±1,6 mm
25 ... 150 Hz 5 g