background image

 

STR100 

10460-0703-00

 

Page

 

5 / 8 

www.ziehl.de 

  

The equipment is built according to  DIN / EN and checked and leave the plant according to security  in 
perfect condition. If, in any case the information in the instructions manual is not sufficient, please contact 
our company or the responsible representative. 
To  maintain  this  condition,  you  must  observe  the  safety  instructions  in  this  instruction  manual  titled 
“Important  Information”.  Failure  to  follow  the  safety  instructions  may  result  in  death,  personal  injury,  or 
property damage to the equipment itself and other equipment and facilities. 
Instead of the industrial norms and regulations written in this instruction manual valid for Europe, you must 
observe out of their geographical scope the valid and relevant regulations of the corresponding country. 

 

Attention! 

If  the  device  is  damaged  it  may  not  be  put  into  operation  if  it  must  be  suspected,  that  a  safe 

operation  may  be  impossible.  The  input  Reset  2  is  not  insulated  from  the  sensor-input.  If  the  sensor  is 
connected with e.g. a heating-element, the input Reset 2 is on the same potential. It has to be made sure that 
this voltage cannot lead up to an electrical shock. 

 

Installation 

The device must be installed within rooms of international protection class IP 5x or better. 
 
The device can be mounted: 

  on 35 mm mounting rail according to EN 60715 

  assembled with screws M4 

  Wiring directly to plug base, connect wires as per wiring scheme 

Apply mains voltage to terminals A1 and A2. The lines of the sensor circuit are to be routed as separate control 
lines 

 
 

Observe  the  maximum  admissible  temperature  when  installing  in  a  switchgear  cabinet. 
Make sure sufficient space to other equipment or heat sources. If the cooling becomes more 
difficult  e.g.  through  close  proximity  of  apparatus  with  elevated  surface  temperature  or 
hindrance  of  the  cooling  air,  the  tolerable  environmental  temperature  is  diminishing. 
Generally recommended minimum clearance is 20 mm. 

 

 
The contacts of the reset push-button at terminal Y1, Y2 must be able to switch low current/voltages. 
We recommend gilded contacts with small bouncing behavior to use. 
 

 

Commissioning 

Attention! 
Temperature relays with supply voltage DC24V without potential separation 
Are intended to use at power supplies SELV or PELV according EN 61558 / EN60742 
where protected wiring is used. 

 

Attention! 
If the internal fuse has triggered, with high probability a failure occurred in the 
Equipment. In this case, the device has to be reviewed and / or repaired in the  
Factory! The device must not be repaired from the user and must be replaced  
With a similar device. 

 
The safety function must be tested additionally to recurring examinations with maintenance services. 
 

- Short circuit test: bypass sensor terminals T1, T2 

 

- Line interruption test: disconnect sensor line at terminal T1 or T2 

If an error is detected no restart must be induced until the error is cleared. 

 

Содержание STR100

Страница 1: ...ehl de Temperature Relays and MINIKA Mains Monitoring Digital Panelmeters MINIPAN Switching Relays and Controls Measuring Transducers Grid and Plant Protection Operating Manual STR100 updated 2020 06 25 sm STR100 10460 0703 00 Page 1 8 www ziehl de Safety Temperature Limiter Supply voltage AC230V Category 3 EN954 1 ...

Страница 2: ...ating conditions commissioning and disposal recycling are not observed the product may not operate safely and may cause a hazard to the life and limb of users and third parties Deviations from the following requirements may therefore lead both to the loss of the statutory material defect liability rights and to the liability of the buyer for the product that has become unsafe due to the deviation ...

Страница 3: ...ding EN 60730 VDE 0631 The temperature is measured with a Pt 100 resistance temperature detector RTD according to EN 60751 IEC 751 The process qualification in combination with the sensor must be proved To fulfil affords for higher safety functionality the function has to be routine tested periodically The thermostat series STR 100 meets safety category 3 Safety of machines EN 954 1 TÜV Rheinland ...

Страница 4: ...ys are locked When temperature is app 10 K below the limit the control relay contacts 6 7 close releases and the green LED is alight The STR 100 now operates in changeable safety mode the relays can be reset manually with built in reset button or with external contact make contact no at terminal Y1 Y2 6 Function Chart 7 Important Information DANGER Hazardous voltage Will cause death or serious inj...

Страница 5: ... assembled with screws M4 Wiring directly to plug base connect wires as per wiring scheme Apply mains voltage to terminals A1 and A2 The lines of the sensor circuit are to be routed as separate control lines Observe the maximum admissible temperature when installing in a switchgear cabinet Make sure sufficient space to other equipment or heat sources If the cooling becomes more difficult e g throu...

Страница 6: ... connection 2 wire Pt100 according EN60751 IEC751 0 00385 max current 3 15 mA 10 mA at 200 0 C max voltage 2 V open terminal 15 V Line compensation normally Standard 0 5 Ω Option up to max 30 Ω Release function Release Over temperature interruption short circuit and malfunction Temperature limit Adjustable see temperature range Accuracy 3 of scale Repeatability 1 Hysteresis 10 C 25 3 C at 200 0 C ...

Страница 7: ... conditions Operating temperature 0 C 50 C EN 60068 2 2 dry heat Storage temperature 20 C 70 C Altitude 2000 m above sea level Vibration resistance 1 mm at 25 Hz 10 g 25 100 Hz Shock resistance 10 g for 20 ms 20 g for 4 ms Housing Construction type S12 Material housing PA 6 6 UL94 V 2 Material socket PA 6 6 GF25 UL94 HB Dimensions H x W x D 82 x 42 x 121 mm IP Code housing IP40 IP Code terminals I...

Страница 8: ...e S12 13 Disposal Disposal should be carried out properly and in an environmentally friendly manner in accordance with legal provisions 104 5 82 36 23 5 5 41 5 80 34 1 2 3 4 5 6 7 8 9 10 11 12 82 41 5 17 7 5 5 11 5 17 5 5 10 14 27 5 41 16 38 61 116 5 3 2 1 1 ...