Connection diagram 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

1) 

Feedback contacts not connected set 

8

rel .

8

 

 

8

trel.

8

 

 

8

 off.

8

 

2) 

Fuses only when line protection necessary, e.g. 3x16A 

3) 

8

Pr 3

8

 Phase connect to L1, L2 and L3 are not connected 

4) 

N connected set 

8

Pr 1

8

8

Pr 3

8

8

Pr 4

8

 

5) 

NC- or NO-contacts can be connected, automatic detection when switching on 

6) 

must be connected for plants 

≥ 20kW

 

 

 

 

Important information 

  

A marked switch and a protective device must be provided in the supply line in the 
vicinity of the device (easily accessible) as a disconnecting element   
(rated current ≤ 6A). 

 

WARNING

 

Hazards electrical voltage!

  

Can lead to an electric shock and burns. 

 

Disconnect and de-energize before working on the system and the device. 

 

Comply with the maximum permissible temperature when installing in a switch cabinet. Ensure 
sufficient clearance to other devices or heat sources. If cooling is inhibited, e.g., through close 
proximity to devices with increased surface temperature or interference with the cooling-air current, 
the permissible ambient temperature is decreased.  

 

 

 

Caution! 

 

 

Before  you  apply  mains  voltage  to  the  device,  make  sure  that  the  permissible  control 

 

     voltage 

Us 

on the side rating plate matches the mains voltage connected to the device!

  

 

 

Assembly 

The device can be mounted: 

  Distribution panel or control panel on 35 mm rail according to EN 60715

 

Содержание SPI1021

Страница 1: ...s status yellow OFF Input not active open ON Input active closed 3 LEDs relay status yellow OFF Relay is released ON Relay is operating 4 Digital display 4 digits red Depending on program display of current voltage frequency vector shift average value Displays the alarm signals e g 8AL 8 8aL M8 Displays the errors with error code e g 8Err98 5 LED Time yellow ON A time is displayed 6 Last decimal p...

Страница 2: ...Input volt free contact 8vsr 8 8 off 8 no function 8vsr 8 8 on 8 E1 E2 closed Vector shift active but not evaluated monitoring of feedback contacts off for use with generator mains synchronization Y0 Y1 Inputs feedback contacts Volt free n o or n c contact self learning when switching on Set value turn on time section switch under 8rel 8 8trel 8 can switch off if not connected or if external devic...

Страница 3: ...8 110 HM Hysteresis V 10 0 17 5 10 0 10 0 17 5 4 3 dal Response time s 3 00 3 00 3 00 3 00 3 00 3 00 dof OFF delay s 0 0 0 0 0 0 U_ 27 S1 27 S1 u_ Alarm on off On On On On On On u_ Undervoltage V 196 339 196 196 339 85 H_ Hysteresis V 8 0 13 5 8 0 8 0 13 5 3 5 dal Response time s 1 50 1 50 1 50 0 40 0 40 1 50 dof OFF delay s 0 0 0 0 0 0 U__ 27 S2 27 S2 u__ Alarm on off On On On On On On u__ Underv...

Страница 4: ...2 vsr Number of phases 3ph 3ph 3ph 3ph 3ph Rocf 81r rocf Alarm on off Off Off Off Off Off Off dfdt delta f delta t Hz s 0 800 0 800 0 800 2 000 2 000 2 000 Per periods 20 20 20 20 20 20 dal Response time s 0 10 0 10 0 10 0 10 0 10 0 10 dof OFF delay s 60 60 60 1 1 1 rEL trEL response time Y1 s 5 0 5 0 Off 5 0 5 0 5 0 Don Delay On s 300 300 300 300 300 300 Mode mode Mode tran tran tran tran tran tr...

Страница 5: ...t 6A WARNING Hazards electrical voltage Can lead to an electric shock and burns Disconnect and de energize before working on the system and the device Comply with the maximum permissible temperature when installing in a switch cabinet Ensure sufficient clearance to other devices or heat sources If cooling is inhibited e g through close proximity to devices with increased surface temperature or int...

Страница 6: ... Only change the parameters after having selected the correct program Putting into operation 8 1 Self test execute In programs 1 3 4 the SPI1021 has an automatic self test as recommended in CEI 0 21 and DEWA K1 can pick up only after the self test has been passed once Self test starts automatically as soon as measuring voltage is connected for the first time to a new device and when there is no al...

Страница 7: ...own simultaneously sets the value to the lowest value Code Reset 2 s Set when mains are switched on Pin 504 Error messages Err5 Internal control Err7 Contactor feedback contacts K1 Err8 Limit error Err9 Parameter error 1 1 3AC N 300V Menu mode Display mode Configuration mode ...

Страница 8: ...ot connected Check for correct connection Set turn on time of section switch under 8trel 8 Do a reset interrupt control voltage for 5s 8Err78 LED K1 flashes und K2 is operating Error when off the section switch Check the connection Check for broken section switch Do a reset interrupt control voltage for 5s 8Err88 appears in the display Hysteresis error Upper threshold value must be higher than the...

Отзывы: