ZIEHL SPI1021 Скачать руководство пользователя страница 4

 

SPI1021 

12570-0751-08

 

Seite

 

4 / 8 

www.ziehl.de 

 

Menu 

item 

Parameter / Unit 

CEI 0-21 

DEWA 

Users 

data 

3AC+N 

230V

 

3AC 

400V

 

1AC+N 

230V

 

3AC+N 

230V 

3AC 

400V 

3AC 

100V 

Pr1  

Pr2 

Pr3 

*

 

Pr4

 

Pr5

 

Pr6

 

 

F_ 

81.S1 

81<S1 

F_

 

Alarm on/off 

 

Off 

Off 

Off 

OFf 

Off 

Off 

 

F_

 

Underfrequency

 

Hz 

49.80 

49.80 

49.80 

47.50 

47.50 

47.50 

 

H_

 

Hysteresis

 

Hz 

0.10 

0.10 

0.10 

0.10 

0.10 

0.10 

 

dal

 

Response time

 

0.10 

0.10 

0.10 

4.00 

4.00 

4.00 

 

dof

 

OFF-delay

 

 

F__ 

81.S2 

81<S2

 

F__

 

Alarm on/off 

 

On 

On 

On 

On 

On 

On 

 

F__

 

Underfrequency

 

Hz 

47.50 

47.50 

47.50 

46.00 

46.00 

46.00 

 

H__

 

Hysteresis

 

Hz 

0.10 

0.10 

0.10 

0.10 

0.10 

0.10 

 

dal

 

Response time

 

0.10 

0.10 

0.10 

10.0 

10.0 

10.0 

 

dof

 

OFF-delay

 

 

UonF

 

UonF

 

Alarm on/off

 

 

Off 

Off 

Off 

On 

On 

On 

 

UonF

 

Spannung 0,2 
Un

 

46 

80 

46 

46 

80 

20 

 

Vsr 

78

 

vsr

 

Alarm on/off

 

 

Off 

Off 

Off 

Off 

Off 

Off 

 

vsr

 

Vector shift

 

°

 

10.0 

10.0 

10.0 

10.0 

10.0 

10.0 

 

dof

 

OFF-delay

 

 

dEon

 

Suppression time 

 

vsr

 

Number of 
phases

 

 

3ph 

3ph 

 

3ph 

3ph 

3ph 

 

Rocf 

81r

 

rocf 

Alarm on/off 

 

Off 

Off 

Off 

Off 

Off 

Off 

 

dfdt 

delta f / delta t

 

Hz/s

 

0.800 

0.800 

0.800 

2.000 

2.000 

2.000 

 

Per 

periods

 

 

20 

20 

20 

20 

20 

20 

 

dal

 

Response time

 

s

 

0.10 

0.10 

0.10 

0.10 

0.10 

0.10 

 

dof

 

OFF-delay

 

s

 

60 

60 

60 

 

rEL 

trEL

 

response time 
Y1 

s

 

5.0 

5.0 

Off 

5.0 

5.0 

5.0 

 

Don

 

Delay On

 

300 

300 

300 

300 

300 

300 

 

Mode 

mode

 

Mode

 

 

tran 

tran 

tran 

tran 

tran 

tran 

 

Dal

,

 

Response time 
(<</>>)

 

1.00 

1.00 

1.00 

1.00 

1.00 

1.00 

 

Dal_ 

Response time 
(<</>>)

 

4.00 

4.00 

4.00 

4.00 

4.00 

4.00 

 

ddi 

ddi

 

Display delay

 

s

 

0.5 

0.5 

0.5 

0.5 

0.5 

0.5 

 

dit

 

Display duration 

SCn 

3.5 

3.5 

3.5 

3.5 

3.5 

3.5 

 

Si 

U

 

Voltage 

 

V

 

230 

400 

230 

230 

400 

100 

 

F

 

Frequency

 

Hz

 

50.00 

50.00 

50.00 

50.00 

50.00 

50.00 

 

vsr

 

Vector shift

 

°

 

0.0 

0.0 

0.0 

0.0 

0.0 

0.0 

 

CodE

 

pin

 

Pincode 

 

504 

504 

504 

504 

504 

504 

 

Info 

fnr

 

Firmware version 

 

0-0D 

0-0D 

0-0D 

0-0D 

0-0D 

0-0D 

 

snr

 

Serial number 

 

xxxxx 

xxxxx 

xxxxx 

xxxxx 

xxxxx 

xxxxx 

 

h

 

Operating hours 

xxxxx 

xxxxx 

xxxxx 

xxxxx 

xxxxx 

xxxxx 

 

err

 

Error counter 

 

xxx 

xxx 

xxx 

xxx 

xxx 

xxx 

 

Pr

 

Program 

 

 

Display program:

8

Info

8

 

 

8

Pr  

8

 

or when switching on, 

Display firmware version:

 

8

Info

8

 

 

8

fnr 

 

 

Содержание SPI1021

Страница 1: ...s status yellow OFF Input not active open ON Input active closed 3 LEDs relay status yellow OFF Relay is released ON Relay is operating 4 Digital display 4 digits red Depending on program display of current voltage frequency vector shift average value Displays the alarm signals e g 8AL 8 8aL M8 Displays the errors with error code e g 8Err98 5 LED Time yellow ON A time is displayed 6 Last decimal p...

Страница 2: ...Input volt free contact 8vsr 8 8 off 8 no function 8vsr 8 8 on 8 E1 E2 closed Vector shift active but not evaluated monitoring of feedback contacts off for use with generator mains synchronization Y0 Y1 Inputs feedback contacts Volt free n o or n c contact self learning when switching on Set value turn on time section switch under 8rel 8 8trel 8 can switch off if not connected or if external devic...

Страница 3: ...8 110 HM Hysteresis V 10 0 17 5 10 0 10 0 17 5 4 3 dal Response time s 3 00 3 00 3 00 3 00 3 00 3 00 dof OFF delay s 0 0 0 0 0 0 U_ 27 S1 27 S1 u_ Alarm on off On On On On On On u_ Undervoltage V 196 339 196 196 339 85 H_ Hysteresis V 8 0 13 5 8 0 8 0 13 5 3 5 dal Response time s 1 50 1 50 1 50 0 40 0 40 1 50 dof OFF delay s 0 0 0 0 0 0 U__ 27 S2 27 S2 u__ Alarm on off On On On On On On u__ Underv...

Страница 4: ...2 vsr Number of phases 3ph 3ph 3ph 3ph 3ph Rocf 81r rocf Alarm on off Off Off Off Off Off Off dfdt delta f delta t Hz s 0 800 0 800 0 800 2 000 2 000 2 000 Per periods 20 20 20 20 20 20 dal Response time s 0 10 0 10 0 10 0 10 0 10 0 10 dof OFF delay s 60 60 60 1 1 1 rEL trEL response time Y1 s 5 0 5 0 Off 5 0 5 0 5 0 Don Delay On s 300 300 300 300 300 300 Mode mode Mode tran tran tran tran tran tr...

Страница 5: ...t 6A WARNING Hazards electrical voltage Can lead to an electric shock and burns Disconnect and de energize before working on the system and the device Comply with the maximum permissible temperature when installing in a switch cabinet Ensure sufficient clearance to other devices or heat sources If cooling is inhibited e g through close proximity to devices with increased surface temperature or int...

Страница 6: ... Only change the parameters after having selected the correct program Putting into operation 8 1 Self test execute In programs 1 3 4 the SPI1021 has an automatic self test as recommended in CEI 0 21 and DEWA K1 can pick up only after the self test has been passed once Self test starts automatically as soon as measuring voltage is connected for the first time to a new device and when there is no al...

Страница 7: ...own simultaneously sets the value to the lowest value Code Reset 2 s Set when mains are switched on Pin 504 Error messages Err5 Internal control Err7 Contactor feedback contacts K1 Err8 Limit error Err9 Parameter error 1 1 3AC N 300V Menu mode Display mode Configuration mode ...

Страница 8: ...ot connected Check for correct connection Set turn on time of section switch under 8trel 8 Do a reset interrupt control voltage for 5s 8Err78 LED K1 flashes und K2 is operating Error when off the section switch Check the connection Check for broken section switch Do a reset interrupt control voltage for 5s 8Err88 appears in the display Hysteresis error Upper threshold value must be higher than the...

Отзывы: