MU1000K
12370-0705-01
Page
8 / 12
www.ziehl.de
6.5 Query firmware version on the device
Query only possible from version 0-04:
•
Keep the [Set] Button pressed (
≥ 5s)
The LEDs indicate the firmware version by flashing rapidly
(binary coded:
LED 300V = Bit0 … LED ON = Bit3)
6.6 Overview of scaling an arbitrary range
Other ranges may be set by scaling of the input signal:
Input (U / I / Pt 100)
Output
Zero point
Full scale
Zero point Full scale
0-10 V
0-10 V
0 V -
10 V
0-20 mA
0-20 mA
2 V -
10 V
-200 - 800 °C
-200 - 800 °C
0 mA -
20 mA
4 mA -
20 mA
6.7
Scaling of range
Parameterization:
•
Power off the device
•
Press Button
[Down]
and keep pressed
•
Power on the device, and keep pressed the button [Down]
After 5s flashes the green LED, release button [Down]
Parameterization
„input type“ >> LED Power flashes 1x
•
Select with button [Set] the input type (displayed by LEDs Pt100 / U / I)
•
Press button [Down]
Parameterization
„input zero point“ >> LED Power flashes 2x
Connect a signal at the input corresponding to the zero point
•
Press button [Down] (store of value, green LED flashes 3 times quickly)
Parameterization
„input full scale“ >> LED Power flashes 3x
Connect a signal at the input corresponding to the full scale
•
Press button [Down] (store of value, green LED flashes 3 times quickly)
Parameterization
„output“ >> LED Power flashes 4x
•
Select with button [Set] the output range
Number of
LED
flashes
U / I
1 x
0 - 10V / 0 - 20mA
2 x
2 - 10V / 4 - 20mA
•
Press button [Down]
End of parameterization, Power LED lights permanently