Information
If you do not use the temperature monitoring, you must switch off the temperature monitoring
(Monitoring/P1P2=Off)
. Short-circuiting of the inputs P1 and P2 is detected as an error by the
ZAdyn4CA HY.
5.4
STO interface (X-STO)
For the use of the "Safe switch-off (STO)" function, please note the information in the operating
instructions R-TBA12_01 (ZAdyn4C).
5.5
DCP-interface (X-DCP)
•
The ZAdyn4CA HY is connected to the elevator control system via DCP4.
•
The ZAdyn4CA HY can only be actuated via the DCP interface with the DCP_04 protocol.
•
Use a shielded cable for the connection. The shielding must be grounded on the inverter side.
•
Con
fi
gure the connection between the ZAdyn4CA HY and the control system without additional
terminal points.
•
The maximum line length is 50 m.
X-DCP
DA
DB
0VD
DATA + (A)
DATA - (B)
GND
(1)
(2)
(3)
(4)
DCP connection
()
terminal designation of connector
Quick Start Guide
ZAdyn4CA HY
Electrical installation
R-TBA16_01-GB 1845 Index 003
Part.-No. 00163456-GB
12/28