Attention!
It is not permitted to connect the connections for automatic addressing (ID1 and ID2) to
the PE conductor or to a voltage potential!
The MODBUS input and MODBUS output interfaces are not identical; please pay
attention to the proper connection (see connection diagram).
6 Communication
6.1 Settings
The device supports baud rates between 4,800-115,200 bit/s, as well as all common
parities and automatic addressing.
The DIP switch S1 (left) is for the baud rate and the DIP switch S2 (right) is for the parity.
Factory setting:
Dip-switches S1 = ON: 19.200
Dip-switches S2 = ON: 8E1
DIP switch position
S1
S2
Coding
1
2
3
Baudrate
Parity
0
OFF
OFF
OFF
4,800 Bit/s
8N1
1
ON
OFF
OFF
9,600 Bit/s
8O1
2
OFF
ON
OFF
19.200 Bit/s
8E1
3
ON
ON
OFF
38.400 Bit/s
8N2
4
OFF
OFF
ON
115.200 Bit/s
-
5
ON
OFF
ON
-
-
6
OFF
ON
ON
-
-
7
ON
ON
ON
-
-
-
No function assigned
Information
Settings that have been changed will only become active after an interruption of the
supply voltage.
Operating Instructions
NETcon
Z-G-1NE
Communication
L-BAL-E244-GB 1732 Index 003
Part.-No.