Diagram setting signal and speed
nM
25.03.2014
v_ecblue_set_min_max.vsd
1
2
3
4
5
6
7
8
9
10
Analog In 1
80
70
60
50
40
30
20
10
0...10 V
10
20
30
40
50
60
70
80
90
100 0...100 % PWM
0
0
90
100 %
n-min 0 % n-max. = 100 %
n-min 40 % n-max. = 90 %
n-min 40 % n-max. = 100 %
nM:
Motor speed
Analog In 1:
Speed setting signal
n-min:
Min. Speed
n-max:
Max. Speed
100 % Rated speed
8.3
Menu group Start
Start
PIN input
The service menu for the installation can be protected against unintentional changes
by a pin code. With further pin codes putting back to pre-setting is possible.
PIN 0010
Release of the service settings with programmed PIN-Accesslevel
|
0
|
(
“
Controller
Setup
”
).
Menu groups Service:
“
Controller Setup
”
,
“
IO Setup
”
,
“
Motor Setup
”
PIN 1234
Opening
“
setting
”
.
Release of the menu group for the user
“
Setting
”
with programmed PIN-Accesslevel
|
0
|
(
“
Controller Setup
”
).
PIN 3698
Communications parameters take-over.
PIN 9095
Loading the factory settings.
Only the parameters which are released by the currently set PIN-Accesslevel are
loaded.
Reset
Complete re-start of the device
Software version
Parameter sets can be saved by the module in the terminal type A-G-247NW and
transferred to other devices (
Operating Instructions Terminal Type A-G-247NW).
Name parameterset with the keys
▼
,
▲
+
P
and load in the terminal with the
P
-key.
Assembly instructions
ECblue
Programming by hand held terminal A-G-247NW
L-BAL-F055D-GB 1634 Index 002
Part.-No.
27/51