Shielding
The use of shielded cables is normally not demanded but offers high protection against electro-
magnetic interferences, especially high frequencies. However, the effectiveness of the shield depends
on careful installation of the line.
If shielded cables are used, the shield should be placed at
“
PE
”
on at least one side (preferably on the
master connection). The occurrence of compensating currents may have to be considered if the shield
is contacted on both sides.
Shield connection correct
Shield connection incorrect
Default interface parameter
Baudrate
=
19200
Bits
=
8
Parity
=
Even (None, exception of devices agriculture)
Stop bits
=
1
Handshake
=
none
Information
If any matters are unclear, please contact our V-STE support department for control systems -
ventilation technology. The information sheet "Network structure of MODBUS" R-TIL08_01 contains
detailed information about "MODBUS".
5.14
Open-Collector output
“
A1
”
(status / tacho)
Open-Collector pulse output for status display or speed display.
Status display
(function for factory setting)
Depending on the operating state of the device, the output
“
A1
”
is switched to
GND potential for a certain number of pulses.
The status of the device can be displayed by this digitally coded signal.
With the output voltage
“
+10 V
”
a standard LED / low-power LED can be
controlled by using a pull-up resistor.
This lights when the output
“
A1 Status Out OC
”
(OC = Open-Collector) is on GND
potential.
The details of which pull-up resistor needs to be used depend on the speci
fi
cation
on the LED that is used.
Explanation of
fl
ash codes
Diagnostic / Status Out with
fl
ash code.
Pull Up
10V
A1
GND
06.11.2013
i_ecblue_a1_status_oc.eps
200...300 Ω
Tacho out
Alternatively, via output
“
A1
”
, the current motor speed can be output.
The frequency (duty cycle 50 : 50) that can be measured by a pull-up resistor at
the output
“
A1
”
corresponds to the motor speed.
Example: 10 Hz x 60 = 600 rpm
Pull Up
10 V
A 1
GND
Hz
n = f x 60
5 kΩ
06.11.2013
i_ecblue_a1_tacho_oc.eps
200...300 Ω
A1
more speci
fi
cations
Technical data!
Assembly instructions
ECblue
Electrical installation
L-BAL-F055D-GB 1634 Index 002
Part.-No.
23/51