Diagnostics / Faults

Operating conditions are indicated by the status LED with 

ashing code.

10.01.2014

v_flash_explain_1_17.vsd

ON

OFF

1 x

16 x

15 x

14 x

13 x

12 x

11 x

10 x

9 x

8 x

7 x

6 x

5 x

4 x

3 x

2 x

17 x

Code

Relay

 K1

Explanation

Reaction of device

Adjustment

OFF

de-energized, 13 - 
14 interrupted

No line voltage 

In the event of a mains interruption the 
unit switches 

OFF

 and automatically 

ON

 when the voltage has been re-

stored. 
Check line voltage and pre-fusing.

ON

energized 13 - 14 
bridged

Normal operation without fault

 

1

energized 13 - 14 
bridged

No enable = OFF 

Terminals 

D1

 - 

24 V

 (Digital In 1) not 

bridged.

Switch off by external contact (

  ena-

ble, device ON / OFF). 

2

energized 13 - 14 
bridged

Temperature management active

The device has an active temperature 
management to protect it from damage 
due to too high inside temperatures. In 
case of a temperature rise above the 

xed limits, the modulation is reduced 

linearly. To prevent the complete system 
being switched off externally (in this op-
eration permissible for the controller) in 
case of reduced operation due to too 
high an internal temperature, no fault 
message is sent via the relay. 

With a drop in temperature the modula-
tion rises again llinear.
Check cooling of the controller.

4

de-energized, 13 - 
14 interrupted

line failure

The device is provided with a built-in 
phase-monitoring function for the mains 
supply. In the event of a mains interrup-
tion (failure of a fuse or mains phase) the 
unit switches off after a delay (approx. 
15 s). 
Only functioning with an adequate load 
for the controller.

Following a shutoff, a startup attempt is 
made after approximately 5  seconds, if 
the voltage supply is high enough. This 
keeps occurring until all 3 supply phases 
are available again.  
Check line voltage.

6

de-energized, 13 - 
14 interrupted

IGBT Fault

Earth fault or short-circuit at inverter out-
put.

The device switches off, renewed at-
tempt to start after about 60 s

  Code 9.

Final switch off when error is detected 
after the third start attempt at an interval 
< 60 s.
Reset by enable or line voltage ON/OFF.

Operating Instructions 

Icontrol Basic

 

 model series FSDM2.6...62

Diagnostics / Faults

L-BAL-E160-GB 1701 Index 004

Part.-No. 

19/28

Содержание iControl FSDM2.6

Страница 1: ...for 3 fans Speed controller with 0 10 V input for presetting the fan speed Operating Instructions Keep for reference Software version D2732A from Version 1 03 L BAL E160 GB 1701 Index 004 Part No engl...

Страница 2: ...4 6 Temperature in uences during commissioning 11 5 Electrical installation 11 5 1 Safety precautions 11 5 2 EMC compatible installation 11 5 2 1 Interference emission and installation of cables 11 5...

Страница 3: ...es 18 6 Start up 18 6 1 Prerequisites for commissioning 18 7 Diagnostics Faults 19 8 Enclosure 22 8 1 Technical data 22 8 1 1 Maximum loading dependent on switching frequency line voltage and ambient...

Страница 4: ...ce of unauthorized repairs or modi cations 1 4 Copyright These operating instructions contain copyright protected information The operating instructions may be neither completely nor partially photoco...

Страница 5: ...ions and skills for these jobs In addition they must be knowledgeable about the safety regulations EU EC directives rules for the prevention of accidents and the corresponding national as well as regi...

Страница 6: ...urer in writing Use only genuine spare parts genuine wearing parts genuine accessories from ZIEHL ABEGG Th ese parts were speci cally designed for the device There is no guarantee that parts from non...

Страница 7: ...0 mA PWM 3 3 Maintenance The device must be checked for soiling and if necessary cleaned in periodic intervals 3 4 Transport The device is packed ex factory to suit the transport method previously agr...

Страница 8: ...cooling air feed as well as unobstructed outgoing air discharge minimum space requirement The device should be installed in a location where it will not be disturbed but at the same time can be easil...

Страница 9: ...29 01 2016 1 3 2 Drill fastening point 1 Screw in at head screw up to a distance of approx 2 mm and mount the device Remove the terminal compartment cover Align the device and mark the position of bo...

Страница 10: ...points GM00002B_M 28 01 2016 1 2 3 4 5 6 8 7 Drill 8 fastening points Screw in fastening point screws 1 4 up to a distance of approx 5 mm and mount the device Tighten fastening point screws 1 4 Screw...

Страница 11: ...and all electrical supply facilities locked Access is only allowed for authorized persons using a key or special tool Operating the device with the housing cover removed is prohibited because energize...

Страница 12: ...m EN 61000 3 12 valid for equipments with rated current 16 A and 75 A connected to public low voltage systems This equipment complies with IEC 61000 3 12 provided that the short circuit power SSC is g...

Страница 13: ...connection The motor leads are connected to the terminals PE U V W Comply with the motor data rating plate regarding the type of connection Y or D U f characteristic curve and technical data Informat...

Страница 14: ...ugged at top factory setting A maximum of six individual thermistors DIN 44081 or DIN 44082 may be connected in series to a single device J1 TP Motor with thermostats TB For motor with thermostats TB...

Страница 15: ...ng 0 10 V factory setting Control via external setting signal 0 10 V or Speed setting by external potenziometer 10 k at terminals 10 V and GND pick of off at terminal E1 E1 D1 GND 0 10 V Analog In 1 E...

Страница 16: ...ical data und connection diagram It is not permissible to connect voltage outputs of several devices to each other It is not permissible to connect voltage outputs in the device to each other 5 9 Volt...

Страница 17: ...troller shunt with mains voltage Mutual locking of mains contactor and bypass protection Time delay of at least 1 second during switching When the contactor is switched off at the inverter output the...

Страница 18: ...rs can be addressed automatically by an additional connection The device can be communicated with using the hand held terminal type A G 247NW Connection by cable via the MODBUS interface or wirelessly...

Страница 19: ...this op eration permissible for the controller in case of reduced operation due to too high an internal temperature no fault message is sent via the relay With a drop in temperature the modula tion ri...

Страница 20: ...ing off of error message when the volt age exceeds the xed limit for at least 5 s Check line voltage 13 de energized 13 14 interrupted Line voltage too high Line voltage above xed limit for longer th...

Страница 21: ...s After every detection IGTB Recovery Flag is set there is a 30 s wait until a new attempt is started The respective errors must alway have a shorter interval than 5 minutes started after restart The...

Страница 22: ...rating plate rated voltage rated temperature cos 0 8 at the output 2 At rated voltage cos 0 8 at the output values for different speci cations on request 3 Example for power of a 4 pole motor For the...

Страница 23: ...ns Interference immunity EN 61000 6 2 industrial applications Harmonics current For devices 16A according to EN 61000 3 2 see Electrical Installation Harmonics current for devices 16A For devices 16 A...

Страница 24: ...50 C 55 C 40 C 50 C 55 C F S DM32A Q 32 0 A 32 0 A 28 0 A 32 0 A 30 0 A 26 0 A F S DM39A Q 39 0 A 39 0 A 39 0 A 39 0 A 39 0 A 37 0 A F S DM46A Q 46 0 A 46 0 A 42 0 A 46 0 A 43 0 A 39 0 A F S DM62A Q...

Страница 25: ...52 7 A 46 7 A 42 5 A 52 7 A 46 7 A 40 8 A Maximum motor current for 16 kHz depending on line voltage and ambient temperature Type 208 V 15 415 V 6 over 415 V 6 480 V 10 40 C 50 C 55 C 40 C 50 C 55 C...

Страница 26: ...bei Q in Typ Main switch only at Q in type 9 1 J1 E1 1 E1 2 TB TP 0 20 mA 0 10 V 10 V PWM 15 28 V PWM 5 6 Temperaturf hler Thermistors TP Thermostatschalter Thermostats TB UMUN11K2 14 01 2016 2 Nicht...

Страница 27: ...FSDM5 FSDM17 FSDM25 FSDM32 FSDM62 Operating Instructions Icontrol Basic model series FSDM2 6 62 Enclosure L BAL E160 GB 1701 Index 004 Part No 27 28...

Страница 28: ...nical support for control systems ventilation technology phone 49 0 7940 16 800 Email fan controls service ziehl abegg de Our worldwide contacts are available in our subsidiaries for deliveries outsid...

Отзывы: