ZIEHL-ABEGG iControl FSDM2.6 Скачать руководство пользователя страница 11

4.4

Outdoor installation

Outdoor installation is possible up to -20 

°

C when the controller supply is not switched off. Installation 

must be protected from the effects of weather as much as possible, including protection from direct 
sunlight!

4.5

Installation location for agriculture 

When using for animal keeping, do not install the device directly in the stable but in a separate room 
with a lower pollutant load. This helps to avoid damages caused by pollutant gases (e.g. ammonia 
fumes, hydrogen sulphide fumes).

4.6

Temperature in

uences during commissioning

Avoid condensation in the controller and functional faults attributable to condensation by storing the 
controller at room temperature!

5

Electrical installation

5.1

Safety precautions

Danger due to electric current

Work on electric components may only be carried out by trained electricians or by persons 
instructed in electricity under the supervision of an electrician in accordance with electrical 
engineering regulations.

The 5 electrical safety rules must be observed!

It is forbidden to carry out work on electrically live parts. Even after disconnection, the dc-link is still 
live. Always wait at least 3 minutes. 

Cover neighbouring electrical equipment during installation work.

Other measures may be necessary to achieve safe electrical isolation.

A second person must always be present when working on energized parts or lines who 
disconnects in case of emergency.

Inspect electrical equipment periodically: retighten loose connections 

 immediately replace 

damaged lines and cables.

Always keep switch cabinets and all electrical supply facilities locked. Access is only allowed for 
authorized persons using a key or special tool.

Operating the device with the housing cover removed is prohibited because energized, exposed 
parts are present inside the device. Disregarding this regulation can lead to severe personal injury.

For metal cable inlets the necessary protective earth connection to the bottom of the housing is 
made by screws. The device may only be started up when these screws are 

tted properly.

The device owner is responsible for the EMC of the entire plant according to the locally applicable 
standards.

Never clean electrical equipment with water or similar liquids.

Information

The respective connections are represented in the enclosure of this manual (

  Connection diagram)!

5.2

EMC-compatible installation

5.2.1

Interference emission and installation of cables

In order to prevent faults attributable to interference and to ensure compliance with the radio interfer-
ence level, the connecting leads must be kept as short as possible both in the motor terminal box as 
well as in the controller. Spacing between supply cables, motor cable and signal cable should thereby 
be kept as large as possible.
The so-called 

pig-tails

 of the screen are to be avoided when connecting screened cables. The 

screen shall be laid close up to the terminals and taken from here to the protective conductor 
connection by the shortest possible route, laid 

at (low induction) and without loops.

When installing the controller in a switching cabinet, attention shall be paid that 

live

 (interference) 

cables and interference-suppressed cables are not routed in the duct. 

Operating Instructions 

Icontrol Basic

 

 model series FSDM2.6...62

Electrical installation

L-BAL-E160-GB 1701 Index 004

Part.-No. 

11/28

Содержание iControl FSDM2.6

Страница 1: ...for 3 fans Speed controller with 0 10 V input for presetting the fan speed Operating Instructions Keep for reference Software version D2732A from Version 1 03 L BAL E160 GB 1701 Index 004 Part No engl...

Страница 2: ...4 6 Temperature in uences during commissioning 11 5 Electrical installation 11 5 1 Safety precautions 11 5 2 EMC compatible installation 11 5 2 1 Interference emission and installation of cables 11 5...

Страница 3: ...es 18 6 Start up 18 6 1 Prerequisites for commissioning 18 7 Diagnostics Faults 19 8 Enclosure 22 8 1 Technical data 22 8 1 1 Maximum loading dependent on switching frequency line voltage and ambient...

Страница 4: ...ce of unauthorized repairs or modi cations 1 4 Copyright These operating instructions contain copyright protected information The operating instructions may be neither completely nor partially photoco...

Страница 5: ...ions and skills for these jobs In addition they must be knowledgeable about the safety regulations EU EC directives rules for the prevention of accidents and the corresponding national as well as regi...

Страница 6: ...urer in writing Use only genuine spare parts genuine wearing parts genuine accessories from ZIEHL ABEGG Th ese parts were speci cally designed for the device There is no guarantee that parts from non...

Страница 7: ...0 mA PWM 3 3 Maintenance The device must be checked for soiling and if necessary cleaned in periodic intervals 3 4 Transport The device is packed ex factory to suit the transport method previously agr...

Страница 8: ...cooling air feed as well as unobstructed outgoing air discharge minimum space requirement The device should be installed in a location where it will not be disturbed but at the same time can be easil...

Страница 9: ...29 01 2016 1 3 2 Drill fastening point 1 Screw in at head screw up to a distance of approx 2 mm and mount the device Remove the terminal compartment cover Align the device and mark the position of bo...

Страница 10: ...points GM00002B_M 28 01 2016 1 2 3 4 5 6 8 7 Drill 8 fastening points Screw in fastening point screws 1 4 up to a distance of approx 5 mm and mount the device Tighten fastening point screws 1 4 Screw...

Страница 11: ...and all electrical supply facilities locked Access is only allowed for authorized persons using a key or special tool Operating the device with the housing cover removed is prohibited because energize...

Страница 12: ...m EN 61000 3 12 valid for equipments with rated current 16 A and 75 A connected to public low voltage systems This equipment complies with IEC 61000 3 12 provided that the short circuit power SSC is g...

Страница 13: ...connection The motor leads are connected to the terminals PE U V W Comply with the motor data rating plate regarding the type of connection Y or D U f characteristic curve and technical data Informat...

Страница 14: ...ugged at top factory setting A maximum of six individual thermistors DIN 44081 or DIN 44082 may be connected in series to a single device J1 TP Motor with thermostats TB For motor with thermostats TB...

Страница 15: ...ng 0 10 V factory setting Control via external setting signal 0 10 V or Speed setting by external potenziometer 10 k at terminals 10 V and GND pick of off at terminal E1 E1 D1 GND 0 10 V Analog In 1 E...

Страница 16: ...ical data und connection diagram It is not permissible to connect voltage outputs of several devices to each other It is not permissible to connect voltage outputs in the device to each other 5 9 Volt...

Страница 17: ...troller shunt with mains voltage Mutual locking of mains contactor and bypass protection Time delay of at least 1 second during switching When the contactor is switched off at the inverter output the...

Страница 18: ...rs can be addressed automatically by an additional connection The device can be communicated with using the hand held terminal type A G 247NW Connection by cable via the MODBUS interface or wirelessly...

Страница 19: ...this op eration permissible for the controller in case of reduced operation due to too high an internal temperature no fault message is sent via the relay With a drop in temperature the modula tion ri...

Страница 20: ...ing off of error message when the volt age exceeds the xed limit for at least 5 s Check line voltage 13 de energized 13 14 interrupted Line voltage too high Line voltage above xed limit for longer th...

Страница 21: ...s After every detection IGTB Recovery Flag is set there is a 30 s wait until a new attempt is started The respective errors must alway have a shorter interval than 5 minutes started after restart The...

Страница 22: ...rating plate rated voltage rated temperature cos 0 8 at the output 2 At rated voltage cos 0 8 at the output values for different speci cations on request 3 Example for power of a 4 pole motor For the...

Страница 23: ...ns Interference immunity EN 61000 6 2 industrial applications Harmonics current For devices 16A according to EN 61000 3 2 see Electrical Installation Harmonics current for devices 16A For devices 16 A...

Страница 24: ...50 C 55 C 40 C 50 C 55 C F S DM32A Q 32 0 A 32 0 A 28 0 A 32 0 A 30 0 A 26 0 A F S DM39A Q 39 0 A 39 0 A 39 0 A 39 0 A 39 0 A 37 0 A F S DM46A Q 46 0 A 46 0 A 42 0 A 46 0 A 43 0 A 39 0 A F S DM62A Q...

Страница 25: ...52 7 A 46 7 A 42 5 A 52 7 A 46 7 A 40 8 A Maximum motor current for 16 kHz depending on line voltage and ambient temperature Type 208 V 15 415 V 6 over 415 V 6 480 V 10 40 C 50 C 55 C 40 C 50 C 55 C...

Страница 26: ...bei Q in Typ Main switch only at Q in type 9 1 J1 E1 1 E1 2 TB TP 0 20 mA 0 10 V 10 V PWM 15 28 V PWM 5 6 Temperaturf hler Thermistors TP Thermostatschalter Thermostats TB UMUN11K2 14 01 2016 2 Nicht...

Страница 27: ...FSDM5 FSDM17 FSDM25 FSDM32 FSDM62 Operating Instructions Icontrol Basic model series FSDM2 6 62 Enclosure L BAL E160 GB 1701 Index 004 Part No 27 28...

Страница 28: ...nical support for control systems ventilation technology phone 49 0 7940 16 800 Email fan controls service ziehl abegg de Our worldwide contacts are available in our subsidiaries for deliveries outsid...

Отзывы: