Diagram: setting signal and output voltage (ohmic load)
U
Out
50 %
100 %
0
1
2
3
4
5
6
7
8
9
10
10
9
8
7
6
5
4
3
2
1
0
0
2
4
6
8
10
12
14
16
18
20
20
18
16
14
12
10
8
6
4
2
0
4
5,6
7,2
8,8
10,4
12
13,6 15,2 16,8 18,4
20
20
18,4 16,8 15,2 13,6
12
10,4
8,8
7,2
5,6
4
0 – 10 V
10 – 0 V
0 – 20 mA
20 – 0 mA
4 – 20 mA
20 – 4 mA
n-min 0 % U
in
n-max. = 100 % U
in
24.10.2011
v_ua_pkdm_101.vsd
Si
n-min 30 % U
in
n-max. = 100 % U
in
n-min 0 % U
in
n-max. = 90 % U
in
n-min 20 % U
in
n-max. = 80 % U
in
n-min OFF
Uout
Output voltage (Motor)
Si
Setting signal
n-min
Setting minimal output voltage
n-max
Setting maximal output voltage
Uin
Line voltage input
n-min OFF
Operation with minimum air switch-off (DIP 5 = ON)
5.7.2
Sensor connection for operation as P-Controller
2.01
...
3.02
For operation as P-Controller (DIP 1 =
|
ON
|
) Analog In 1
|
E1
|
preset for operation as Pressure
controller for condensers (DIP 2 =
|
OFF
|
) with 4 - 20 mA input. By the internal dipswitches further
settings are possible (
basic settings).
Signal type at E1 (E2)
DIP 3 =
|
OFF
|
*
for Pressure control (DIP 2 =
|
OFF
|
): 4 - 20 mA (
e.g. for pressure sensor type MBG..
)
for Temperature control (DIP 2 =
|
ON
|
): type TF..(KTY81-210)
DIP 3 =
|
ON
|
for Pressure control (DIP 2 =
|
OFF
|
): 0 - 10 V
for Temperature control (DIP 2 =
|
ON
|
): PT1000
Input E2
DIP 7 =
|
OFF
|
*
Input E2 not active
DIP 7 =
|
ON
|
Input E2 active (function
DIP 3)
The controller works automatically at the input with the higher sensor value (E1 or E2).
E.g. for dual circuit condensers in refrigeration technology with two sensors. Automatic control
to sensor which is measuring the higher pressure.
*
factory setting
•
When connecting
passive
temperature sensors type TF.. (KTY81-210) or PT1000 at terminals
“
E1
/ T
”
and/or
“
E2 / T
”
must be paid attention to no polarity.
For a high interference immunity a capacitor must be connected directly to the sensor (1 nF
parallel). With temperature sensors type TF.. (KTY81-210) a capacitor is integrated.
•
When connecting
aktive
sensors at the terminals
“
E1 / GND
”
and/or
“
E2 / GND
”
attention must be
paid to correct polarity, a 24 V DC power supply is integrated.
•
For sensors in two-wire-technology (4 - 20 mA signal), the connection is made on the
“
E1 / 24 V
”
and/or
“
E2 / 24 V
”
,
“
GND
”
terminal is omitted.
Operating Instructions
Dcontrol
–
model series PKDM6..80
Electrical installation
L-BAL-E143-GB 1914 Index 009
Part.-No.
15/40