7 Base setup
7.1 Programming of the desired function (Speed controller / P-Controller)
•
It is possible to use the device as a
“
Speed controller
”
or as a
“
P-controller
”
. Selection of the
function must
rst be made by setting the internal jumper
“
E1
”
and dipswitch
“
S1
”
.
•
Factory setting of internal jumper
“
E1
”
in position for 0 - 10 V input signal.
When using
other signals bring the jumper in correct position.
•
Factory setting of all dipswitches is
|
OFF
|
position for operation as Speed controller
1.01
with external setting signal.
In the following the fundamental dipswitch positions for
further modes of operation are represented. Depending upon desired function further adjust-
ments are necessary (
F
function dipswitches).
Attention!
Setting of jumper and switches not under voltage! Observe the safety notices!
Changed functions become active partly only after renewed switching on the mains voltage!
E1 Analog In = (factory setting 0 - 10 V)
21.07.2008
v_pke_jumper_e1_dip_s1_mode.vsd
A
E1
GND
0 - 10 V
10 k
E1
GND
TF..
TF.. (KTY)
3
1
BN
GN
24V
E1
MBG..
4 - 20 mA
(0 - 20 mA)
4 - 20 mA
E1
E1
0 - 10 V
E1
1.01
2.01
3.01
ON
OFF
4
3
2
1
S1
ON
OFF
4
3
2
1
S1
ON
OFF
4
3
2
1
S1
7.2 Select operation mode
Simple installation is possible through the use of modes of operation.
Mode
Signal or Sensor
(input)
Function
1.01
Signal 0 - 10 V
Speed controller, two step operation (factory setting)
2.01
Sensor TF.. (E1)
Temperature control airconditioning and refrigeration
3.01
Sensor MBG.. (E1)
Pressure control condensers (refrigeration)