4 Mounting
4.1 General notes
Attention!
The following points must be complied with during the mechanical installation to avoid
causing a defect in the device due to assembly errors or environmental in
fl
uences:
•
Before installation remove the device from the packing and check for any possible
shipping damage! Start-up is not allowed in the case of transport damage!
•
At a weight greater than 25 kg for men / 10 kg for women, the device should be lifted
out by two persons (according to REFA). The values may differ from country to
country.
•
Wear safety shoes and gloves for handling!
•
Assemble the device on a clean and stable base. Do not distort during assembly! Use
the appropriate mounting devices for proper installation of the unit!
•
Do not mount equipment on vibrating base!
•
When mounted onto lightweight walls, there must be no impermissibly high vibrations
or shock loads. Any banging shut of doors that are integrated into these lightweight
walls, can result in extremely high shock loads. Therefore, we advise you to decouple
the devices from the wall.
•
Do not allow drilling chips, screws and other foreign bodies to reach the device
interior!
•
The device should be installed in a location where it will not be disturbed, but at the
same time can be easily accessed!
•
Depending on the housing model use supplied stoppers for cable inlets, cut off
necessary cable inlets respectively to the cable diameter. Or alternative use cable
inlet for cable glands. Any cable ducts openings not used must be sealed!
•
Care must be taken to avoid direct radiation from the sun!
•
The device is designed for vertical installation (bottom cable inlet). A horizontal or
reclined installation is only permissible after technical release of the manufacturer!
•
Be sure to observe proper heat dissipation (see Technical data, heat dissipation).
4.2 Minimum space requirement
In order to ensure suf
fi
cient ventilation of the device, clearance on all sides of at least
50 mm has to be maintained to the housing walls, switch cabinet doors, wiring ducts, etc.
The same clearance applies to the installation of several devices next to each other.
When installing several devices on top of each other, the danger of reciprocal heating
exists. This layout is only then permissible when the air suctioned from the upper unit
does not become warmer than the permissible ambient temperature (see Technical
data). I.e., a correspondingly larger clearance or thermal shielding is required.