Input resistance for speed setting
signal
for 0...10 V input: R
i
> 100 k
Ω
for 0...20 mA input: R
i
= 100
Ω
Voltage supply for external devices
+24 V
±
20 %, I
max
70 mA
Heat dissipation in standby opera-
tion
approx. 3 W
Output 10 V
I
max
10 mA (short-circuit-proof)
Digital input
“
D1
”
Input resistance: R
i
approx. 4 k
Ω
Voltage range high level: 10....30 V DC
Voltage range low level: 0....4 V DC
Max. contact rating of the relay
2 A / 250 VAC
Max. permissible ambient tempera-
ture
55
°
C
Min. permissible ambient tempera-
ture
0
°
C (if mains voltage is not switched off up to -20
°
C)
To avoid condensation the device must be continuously energized due to
the application of heat, with interruptions such that cooling to the point of
condensation does not occur.
Permissible temperature range for
storage and transport
-30...+80
°
C
Max. permissible installation height 0...4000 m amsl
above 1000 m amsl the rated current is to be reduced by 5 % / 1000 m
Permissible rel. humidity
85 % no condensation
Electromagnetic compatibility for the
standard voltage 230 / 400 V ac-
cording to DIN IEC 60038
Interference emission EN 61000-6-3 (domestic household applications)
Interference immunity EN 61000-6-2 (industrial applications)
Harmonics current
For devices
≤
16A according to EN 61000-3-2 (see Electrical Installation /
Harmonics current for devices
≤
16A)
For devices > 16 A and
≤
75 A according to EN 61000-3-12 (see Electrical
Installation / Harmonics current and line impedance)
Max. leakage current according to
the de
fi
ned networks of
DIN EN 60990
FSDM2.6/3.6/5/7/8.5 < 3.5 mA
FSDM12/17/25/32/39/46/62 > 3.5 mA
Vibratory strength
(for vertical installation, i.e. cable
inlet down).
Broadband noise (simulated life-endurance test) in accordance with
EN 61373, category 1 class B.
Shock test according to EN 61373, category 1
Max. cross section/diameter of the
conductors for line and motor con-
nection
Conductor cross section single-wire 4 mm
2
Conductor cross-section
fi
ne-wire: 4 mm
2
, with wire end ferrule 2.5 mm
2
Conductor (AWG): 12
Housing protection
IP54
*
Regarding the mains connection, these devices are to be classi
fi
ed as category
“
C2
”
devices according to the relevant
EN 61800-3. The increased requirements placed on electrical interference > 2 kHz for category
“
C1
”
devices are complied
with in addition.
**
Factory setting (possible setting by add-on module for communication).
Operating Instructions
Icontrol Basic
–
model series FSDM2.6...62
Enclosure
L-BAL-E160-GB 1701 Index 004
Part.-No.
23/28