Trouble Shooting
Malfunction
Cause
Remedical Action
Machine operates, but no ice production
Drive motor and
Loss of refrigerant
refrigeration unit work
(ventilator runs)
Refrigeration unit stopped
* No water in water chamber
See water pressure or water level switch
or works at intervals
above
(drive motor runs)
* Motor cut-out defective
Check / replace
* Compressor defective
Check / replace
Decreased ice production
*
Condenser soiled or insufficient
Clean with brush or compressed air,
Poor ice quality
cooling-water flow
never with a wire brush. Water-cooled
machines: bottle brush, antilime agent
* Ambient temperature too high
Provide better ventilation,
move maschine away from wall.
* Insufficient amount of refrigerant,
Remove leak, evacuate circuit,
bubbles in sight glass
replace filter drier, refill with
indicated quantity of refrigerant.
* Lime deposit on auger
Clean freezing unit with hot water and
or cylinder
antilime agent (Ziegra cleaning agent),
clean mechanically, if required.
* Ice breaker is misadjusted
see istallation sheet freezing unit
-ZBE 30-110
* Machine runs in intervals
see above (refrigeration unit stopped)
If Ice maker is connected
* no sufficient refrigerant
check the cooling system of the
to a central refrigeration unit:
* Suction pressure too low
central refrigeration unit
Machine runs in intervals
* pressure fluctuation
Data must comply to the ZIEGRA prescription
(If not at hand, ask Ziegra)
Rumbling or loud squeaking
*
Air bubble in pipe between water
Remove air bubble
noise
chamber and freezing unit
Strong vibrations
Machine freezes up
*
Lime deposit on auger or
Clean freezing unit with hot water and
cylinder
antilime agent, clean mechanically,
if required.
Occasional gentle squeaking noises
are a typical sign for good and hard ice,
but do not indicate a failure.
Cracking noise in the
Cylinder bearing defective
Replace
freezing unit
Ice comes out of machine
Even small edges or bends can be
in pressed form
the cause (see page 2)
("sausages")
6
Repairs of electrical parts and refrigeration circuit only carried out by a
qualified technician!
Check refrigeration circuit (bubbles
in sight glass). Eliminate leakage,
replace filter drier, evacuate circuit,
refill refrigerant.
After leaving the cylinder the ice is
pressed due to wrong installation of the
ice discharge tube, the extension, or
due to sharp bends.