Table 2
Lower value of the alarm
1, 2, 3, 4 switching
-144.0...144.0 %
99.0 %
Upper value of the alarm
1, 2, 3, 4 switching
-144.0...144.0 %
101.0 %
Switching delay of the
alarm 1, 2, 3, 4
0...900 seconds
0
Switching-off delay of
the alarm 1, 2, 3, 4
0...900 seconds
0
Deadlock of alarm
1,2,3,4 re-switching
0...900 seconds
0
Quantity on the con-
tinuous output No 1,
2, 3, 4
0...35 (acc. to the table 1)
24
Lower value of the
input range in % of the
rated range of the input
No 1, 2, 3, 4
-144.0...144.0 %
0.0%
Upper value of the
input range in % of the
rated range of the input
No 1, 2, 3, 4
-144.0...144.0 %
100.0%
Lower value of the out-
put range of the output
No 1, 2, 3, 4
- 20.00...20.00 mA
0.00 mA
Upper value of the
output range of the
output No 1
0.01...20.00 mA
20.00 mA
Manual switching of
the analog output 1, 2,
3, 4 on:
normal work,
the lower value of the output
range is set up,
the upper value of the output
range is set up.
normal work
Pulse quantity for pulse
output
5000 - 20000
5000
Address in the
MODBUS network
1... 247
1
Transmission mode
8n2, 8e1, 8o1, 8n1
8n2
Baud rate
4800, 9600, 19200, 38400
9600
27
27
Содержание CON-M 22
Страница 1: ...ZIEGLER CON M PROGRAMMABLE MULTI TRANSDUCER OPERATING MANUAL 15001298_Rev _B_04 2014 ...
Страница 2: ......
Страница 7: ...4 2 External Connection Diagrams Fig 2 Connection Diagrams of transducer outputs and Rs485 7 7 ...
Страница 8: ...Direct measurement in a four wire network Multi transducer 8 8 ...
Страница 9: ...Measurement with the use of current transformers in a four wire network Multi transducer 9 9 ...
Страница 17: ...Fig 9 Con guration of the connection with the Multi transducer Multi transducer 17 17 ...
Страница 57: ...57 57 NOTE ...
Страница 58: ...58 58 NOTE ...
Страница 59: ...59 59 ...
Страница 60: ...60 60 NOTE ...