Fig.11. View of the conguration window of measurement parameters
5.4.2 Setting of Measurement Parameters
After choosing the group: Meter parameters following elements can be
congured (g. 11.):
a)
Current transformer ratio. The multiplier is used to
recalculate
the current in the transformer primary
side. It is set up on 1 by the manufacturer.
b)
Voltage transformer ratio. The multiplier is used to
recalculate
the voltage in the transformer primary
side. It is set up on 1 by the manufacturer.
c)
Way to synchronize the mean power:
-
15 minutes’ walking window – mean power PAV
will be recalculated for the last 15 minutes, actualized
every 15 seconds, i.e. walking window,
- measurement synchronized with the clock every 15, 30
or 60 minutes - mean power PAV
will be actualized every
15, 30 or 60 minutes synchronized with the external real
clock (g. 12).
It is set up on the walking window by the manufacturer.
19
19