  Wiring Condition    Display Indication 

N    G    H 

Correct Wiring                     ●    ●    ●    

No Ground                   ●   

    ●       

Polarity Reversal              ¤    ●      ¤       

Open/Hot Neutral            

   

   

     

Legend: ●  On   

  Off    ¤  Flashing 

If  the  wiring  condition  is  other  than  normal,  the  Test  is 

limited on its measurements that can be performed. If a 

no  ground  condition  exists,  only  the  line  voltage 

measurements are available.   

 

Notes:   

1) Will not detect two hot wires in a circuit. 

2) Will not detect a combination of defects. 

3) Will not detect reversal of grounded and   

      grounding conductors. 

Voltage test: 

Never apply voltages exceeding 300V to input sockets. 

Connect mains lead (13) to the mains connector 

Select function V via the function switch 

Connect the test leads /mains plug to UUT 

Содержание ZI-9500

Страница 1: ...www zicotech com RCD tester Residual Current Device circuit breaker...

Страница 2: ...differential protection mechanisms At the end of the test there is therefore no power on the tested port of the installation Before using the appliance you must therefore ensure that the absence of po...

Страница 3: ...the interpretation of the measurements This appliance is fitted with Ni MH batteries Comply with the national waste disposal instruction PARTS CONTROLS 1 Digital Display 2 0 180 Button 3 Test Button...

Страница 4: ...d in mA This enables 10mA 30mA 100mA 300mA 500mA and 1000mA differential circuit breakers to be tested irrespective of their type normal or delayed s This comprehensive appliance can also be used to t...

Страница 5: ...If a no ground condition exists only the line voltage measurements are available Notes 1 Will not detect two hot wires in a circuit 2 Will not detect a combination of defects 3 Will not detect reversa...

Страница 6: ...elayed or not together with the type of test that you are required to perform trip time or current You make the selections by pressing the buttons under each columns The characteristics are selected o...

Страница 7: ...3 Selecting 0 or 180 RDDs can react differently depending whether the default current starts with a positive half cycle 0 or a negative half cycle 180 The tester automatically sets itself to a current...

Страница 8: ...ymbol appears on the LCD the six 1 5V AA batteries must be replaced 2 Remove the screw holding the battery cover 3 Remove the battery compartment cover 4 Replace the batteries observing polarity 5 Aff...

Страница 9: ...500 ms at 1x 10 150 ms at 2x 10 40 ms at 5x 1ms 2 rdg 2Digits Ramp test 0 4 x to 1 4 times nominal rated current 10 Mains voltage 230 10 10 V 1v 2 rdg 2Digits Cat III 600V Double insulation IEC 61010...

Страница 10: ...Resistance to mechanical shock 1J Weight 700g Dimensions w 92mm l 200mm h 50mm Six 1 5V AA batteries www zicotech com...