Operation Manual 

 
 

 

 

 

 

ZGR INFLUENCE 10 - 40 KVA 

Online three-phase UPS 

 

 

www.zigor.com

 

 

Содержание INFLUENCE

Страница 1: ...Operation Manual ZGR INFLUENCE 10 40 KVA Online three phase UPS www zigor com...

Страница 2: ......

Страница 3: ...Maintenance mode Manual Bypass 10 Turn on off UPS 11 3 2 1 Initial power up procedure 11 3 2 2 Test procedure 12 3 2 3 Maintenance bypass 12 3 2 4 Cold Start procedure 13 3 2 5 Shut down procedure 14...

Страница 4: ...ions of ZGR INFLUENCE 10 40 KVA 39 Recommended spare parts 40 8 MAINTENANCE 41 Battery maintenance 43 9 TECHNICAL SPECIFICATIONS 45 10 STANDARDS 47 11 WARRANTY 48 2022 ZIGOR All rights reserved The to...

Страница 5: ...assume exclusive responsibility for any risk The use for which the unit was designed is defined in the documentation The system shall be exposed only to admissible environmental conditions These are...

Страница 6: ...ing safety please well earth the UPS before starting it Do not throw batteries into a fire as they may explode UPS models with internal batteries can be powered even when the UPS input is not connecte...

Страница 7: ...pal waste at the end of its useful life To preserve the environment manage them in accordance with current environmental regulations and requirements in each country or community In case of doubt cons...

Страница 8: ...erial delivered corresponds to the delivery note Check the manufacturer s label placed at the rear or on one side of the unit Responsibility for the loss or damage of products shall transfer to the Cu...

Страница 9: ...ortion THD noise interference frequency fluctuation etc This UPS can be applied to different applications from computer device automatic equipment communication system to industry equipment They are a...

Страница 10: ...t 6 Parallel port 2 7 RS232 comm port Only used on internal battery models 9 Remote EPO port 10 Mains breaker 11 Terminal block 12 Cold Start button 13 History logger port 14 Intelligent slot 1 15 Mai...

Страница 11: ...INFLUENCE 10 40 KVA is a double conversion on line UPS that may operate in the following alternative operation modes 3 1 1 Normal mode The rectifier charger derives power from the AC Mains and supplie...

Страница 12: ...be less than an electrical cycle e g less than 15 ms 50 Hz or less than 13 33 ms 60 Hz Fig 3 3 Bypass mode 3 1 4 ECO Mode When the UPS is at AC Mode and the requirement to the load is not critical th...

Страница 13: ...ut off internal battery current drain during storage or transpor It is used only by internal battery UPS models If external battery cabinet is used this switch must be always ON WARNING Make sure grou...

Страница 14: ...es 1 Switch off the mains power to UPS to simulate utility failure the rectifier will turn off and the battery should feed energy through the inverter without interruption At this time the on battery...

Страница 15: ...hrough the MAINTENANCE breaker 3 2 4 Cold Start procedure 1 Turn ON Power Switch on rear panel power will feed from battery to internal electronics Only valid for internal battery UPS On external batt...

Страница 16: ...Battery mode 1 Turn OFF Power Switch on rear panel power will feed from battery to internal electronics Only valid for internal battery UPS On external battery models this switch needs to be always ON...

Страница 17: ...the LCD screen the following elements and areas are shown Fig 4 2 Fig 4 2 Distribution of the control panel window From any window click the main block to enter the main data display window click ret...

Страница 18: ...low chart and there are the data entrance of input output battery Fig 4 3 Fig 4 3 Sys status menu 4 1 1 1 Bypass submenu Click the bypass block to enter the bypass data display window Fig 4 4 Fig 4 4...

Страница 19: ...enter the output data display window Fig 4 6 Fig 4 6 Output submenu 4 1 1 4 Battery submenu Click the battery block to enter the battery data display window Fig 4 7 Fig 4 7 Battery submenu 4 1 2 Run i...

Страница 20: ...4 9 Fig 4 9 Status data window Click on the ENV data icon to enter the status data window the user can see the temperature data after connected to temperature sensor Fig 4 10 Fig 4 10 Temperature data...

Страница 21: ...menu 4 1 3 2 History submenu Click the history to enter the history recode display window Fig 4 13 Fig 4 13 Alarm History submenu 4 1 3 3 Buzzer submenu Click the buzzer mute then the buzzer will mute...

Страница 22: ...ZGR INFLUENCE 10 40 KVA Operation manual www zigor com 20...

Страница 23: ...about advanced settings Fig 4 16 Fig 4 16 Settings menu 4 1 5 Maint menu In this menu the Maintenance settings can be adjusted the touch correction adjusted and done a battery self test Fig 4 17 Fig...

Страница 24: ...int Battery Self Check Timing daily submenu Timing weekly Modify the check date time and check time 10S default 10min EOD Fig 4 20 Fig 4 20 Maint Battery Self Check Timing Weekly submenu 4 1 6 Functio...

Страница 25: ...is starting up Extinguish X X Extinguish 9 ECO Mode Extinguish X X X 10 EPO Mode Light Extinguish X Extinguish 11 Maintenance Bypass Mode Extinguish Extinguish Extinguish Extinguish 12 Fault Mode Lig...

Страница 26: ...d Fault LED blinking 27 Mains Site Wiring Fault Once per second Fault LED blinking 28 Bypass Site Wiring Fault Once per second Fault LED blinking 29 Output Shortcut Once per second Fault LED blinking...

Страница 27: ...re is within the required specs Temperature is a major factor in determining battery life and capacity In a normal installation the battery temperature is maintained between 15 C and 25 C Keep batteri...

Страница 28: ...es for the equipment to be installed External Battery The UPS and its associated batteries are protected against the effect of over current through a DC compatible thermo magnetic circuit breaker or a...

Страница 29: ...lly positioned and secured connect the power cables as described in the following procedure Verify the UPS is totally isolated from its external power source and also all power isolators of the UPS ar...

Страница 30: ...under the terminal block 30 kVA and40 kVA Fig 5 2 Common input connection 30 40KVA Terminal sequence from left to right Input phase A L1 input phase B L2 input phase C L3 input Neutral line output pha...

Страница 31: ...r 10 30 kVAs UPS As default all UPS will be set in factory based on customer needs All related settings can be modified by LCD display menu All this adjustments must be done by trained and authorized...

Страница 32: ...S parallel Installation A group of paralleled UPS behaves as one large UPS system but with the advantage of presenting higher reliability In order to assure that all UPS are equally utilized and compl...

Страница 33: ...attery 5 7 2 Parallel cable installation Shielded and double insulated control cables must be used to interconnect in a ring configuration between UPS units as shown below Fig 5 7 This ring configurat...

Страница 34: ...5 8 User set menu location 3 Fig 5 9 It could be necessary a Service password to operate Only authorized personal may change this configuration Contact ZIGOR for support Fig 5 9 User set window 4 sho...

Страница 35: ...S will show it unique ID on LCD screen 8 Now it can be closed output breakers Communications 5 8 1 USB communication port definition USB communication port definition Fig 5 12 Communication data forma...

Страница 36: ...2 RS232 communication port Communication data format Baud rate 9600bps Byte length 8bit Stop bit 1bit Parity check none Fig 5 13 RS232 pinout definition Connection between PC RS232 port and UPS RS232...

Страница 37: ...in 2 4 Pin 2 4 485 B Pin 7 Pin 7 12 V DC Pin 8 Pin 8 GND Table 5 5 RS485 connections Available function of RS485 Monitor UPS power status Monitor UPS alarm info Monitor UPS running parameters Timing o...

Страница 38: ...2 V Pin 8 Pin 8 GND Table 5 6 BAT_T port definition Available function of BAT_T Battery environment temperature monitoring Charging voltage modulation depending on batteries temperature 5 8 5 Dry cont...

Страница 39: ...n 2 GND Table 5 8 REPO connection A remote emergency stop switch can be installed in a remote location and connection through simple wires to the REPO connector The remote switch can be connected to s...

Страница 40: ...eration manual www zigor com 38 A baud rate choose 9600 protocol Fig 5 19 Fig 5 19 Communication configuration parameters On the main page of Muser4 Fig 5 20 Fig 5 20 Adding an equipment Fig 5 21 Fig...

Страница 41: ...tFeeler Lite to detect temperature humidity smoke and security sensors Thus making NetAgent II a versatile management tool NetAgent II also supports multiple languages and is setup for web based auto...

Страница 42: ...e UPS does not indicate any failure but output do not have voltage Output cable does not well connected Output breaker do not switch on Make sure the output cable is well connected Switch on the outpu...

Страница 43: ...ontinuously and LCD indicates 1 3 5 9 15 etc fault codes UPS is out of order Consult with ZIGOR for repair Table 6 1 Trouble shooting Given the complexity of the equipment when a serious error occurs...

Страница 44: ...tasks in accordance with frequency are as follows Monthly o Visual control of correct operation LEDs indicating correct operation Values within margins No active event o Control of the event history...

Страница 45: ...to see if there is any fault occurred fault indictor is on or any alarm there o Please find the cause if the UPS is working in bypass mode o If the UPS is working in battery mode make sure it is norma...

Страница 46: ...as to keep battery in good condition 1 The most proper working temperature is 15 to 25 C 2 Avoid small discharging current rs 3 Charge battery for at least 12 hours every 3 months if it is free of ope...

Страница 47: ...ZGR INFLUENCE 10 40 KVA Operation manual www zigor com 45...

Страница 48: ...5 default 15 min 20 30 45 default 45 Frequency synchronize tracing range 10 THDI 3 100 non lineal load Generator input Support OUTPUT ELECTRICAL CHARACTERISTICS Phases Three phase N ground Output volt...

Страница 49: ...immediately Bypass Mode Breaker 20 A Breaker 32 A Breaker 40 A Breaker 63 A Breaker 80 A Audible Visual Alarms Line Failure Battery Low Overload System Fault MECHANICAL AND ENVIRONMENTAL CHARACTERISTI...

Страница 50: ...ith the following European regulations I LVD Security directive LVD 2014 35 EU about Uninterruptible Power Supply UPS Standard EN IEC 62040 1 2019 II EMC directive 2014 30 EU about electromagnetic com...

Страница 51: ...nnual referring to the Installation Conditions When the customer not clearly proves the systematic realization of regular maintenance operations described in the Operating Manual Equipment deteriorati...

Страница 52: ...zigor com Consulte nuestra web para contactar con la red de delegaciones comerciales Refer to our website in order to contact the commercial branches network Veuillez consulter notre page web pour con...