PROFILE Fire detection system
FBI800
Fixing instructions Doc. version 1.0
3/8
3 Set the optional SW3 DIP switches 7, 8
according to project configuration. Refer to
Table 3.
4 The FBI800 slot card is pre-assembled. To
mount it, line it against the side rails of the
slot in the backplane cage. Slide the card
backwards until it clicks and ensure that it fits
firmly. For more information on slot cards,
see the PROFILE panel Product Application
and Design Information.
5 Connect the Fire Brigade peripherals. Refer to
Figures 3 to 6.
Firmware Update
If a firmware update is required, refer to the
steps in the relevant Technical Information Bulle-
tin (TIB).
Table 3 lists the DIP switch settings for a firm-
ware update. The operational default settings of
the DIP switches
are marked by *.
Slot card addressing
One FBI800 card can be installed in the control
panel. The FBI800 has its own configured sys-
tem address. Refer to Table 4 for the decimal to
binary conversion
Jumper
1 – 2
2 – 3
OPEN
J2 RL1
Normally
closed con-
tact
Normally
open con-
tact *
---
Table 2: Jumper setting for installation.
SW3
Function
ON
OFF
1
2
3
4
DIP1
DIP2
DIP3
DIP4
Reserved*
Reserved
Reserved
Reserved
Reserved
Reserved*
Reserved*
Reserved*
5
Boot Mode
Active
Disabled *
6
Debug
Mode
Enabled
Disabled *
7
EA Door
EA signal
activates
the FBKD
door opener
output
EA signal
doesn’t acti-
vate the
FBKD door
opener *
Table 3: SW3 DIP Switch settings
8
FIC TU
FIC signal
activates
the TUA-
CLED out-
put
FIC signal
doesn’t acti-
vate the
TUACLED
output *
J2 RL1 jumper defines the normal state
of relay RL1 contacts (relay is not
energized).
Address
DIP Switch
1 2 3 4 5 6 7 8
001
1 0 0 0 0 0 0 0
002
0 1 0 0 0 0 0 0
003
1 1 0 0 0 0 0 0
004
0 0 1 0 0 0 0 0
005
1 0 1 0 0 0 0 0
006
0 1 1 0 0 0 0 0
007
1 1 1 0 0 0 0 0
008
0 0 0 1 0 0 0 0
009
1 0 0 1 0 0 0 0
010
0 1 0 1 0 0 0 0
011
1 1 0 1 0 0 0 0
012
0 0 1 1 0 0 0 0
013
1 0 1 1 0 0 0 0
014
0 1 1 1 0 0 0 0
015
1 1 1 1 0 0 0 0
016
0 0 0 0 1 0 0 0
017
1 0 0 0 1 0 0 0
018
0 1 0 0 1 0 0 0
Table 4: FBI800 Decimal to binary DIP switch address con-
version
Table 3: SW3 DIP Switch settings