background image

PROFILE Fire detection system 

FBI800

Fixing instructions  Doc. version 1.0

1/8

FBI800 Fire Brigade Interface Card

Part No. 557.202.845

Introduction

The FBI800 is suitable for use with the Profile 
Pro range of panels.The FBI800 performs the fol-
lowing functions:

Connects the serial Fire Brigade Panel (FBF/
FAT) according to DIN 14661 / DIN 14662 
standards via redundant serial interfaces and 
redundant monitored 24V power supply 
paths. 

Connects the parallel Fire Brigade Panel (FBF) 
according to DIN 14661 standard.

   FBI800

REDB1 A
REDB1 B

REDB2 A

REDB2 B
PWR1+

PWR1-

PWR2+

PWR2-

HEAT+

HEAT-
DO PWR+

DO PWR-

DO CNT+

DO CNT-

SB LP+
SB LP-

SB LED+

SB LED-

CNOFLED

TUOFLED
FIALLED

ASOFLED

TUACLED

EXACLED

PWR+
PWR-

RL1 C

RL1 0/C

FIALRST
AS OFF

REV ON

TU OFF
FIC

TU +a

TU -b

TU PWR+

Status

Card Fault

Reset

 

 

 

 

 

 

 

A d d r e s s

1

0

1

2

3

4

5

6

7

Fig. 1: FBI800 Fire Brigade Interface card
1 – Serial FBF / FAT connector
2 – Fire Brigade Key Depot connector
3 – Parallel FBF + RL1 connector
4 – Parallel FBF + Transmit Unit connector
5 – Optical  indicators
6 – Reset  button
7 – Slot card address DIP switch

2

3

4

5

Fig. 2: FBI800 terminals, LEDs and jumpers
1 – Indicators RX, TX for Bus1 (left channel) 
2 – Indicators RX, TX for Bus2 (right channel)
3 – J2 RL1contact configuration jumper
4 – SW3
5 – XP2 Debug port (RS232)

6 – F200 (FU1) non-replaceable fuse

6

1

Содержание PROFILE FBI800

Страница 1: ...EDB2 B PWR1 PWR1 PWR2 PWR2 HEAT HEAT DO PWR DO PWR DO CNT DO CNT SB LP SB LP SB LED SB LED CNOFLED TUOFLED FIALLED ASOFLED TUACLED EXACLED PWR PWR RL1 C RL1 0 C FIALRST AS OFF REV ON TU OFF FIC TU a TU b TU PWR Status Card Fault Reset A d d r e s s 1 0 1 2 3 4 5 6 7 Fig 1 FBI800 Fire Brigade Interface card 1 Serial FBF FAT connector 2 Fire Brigade Key Depot connector 3 Parallel FBF RL1 connector 4...

Страница 2: ...e earth stud or follow the manufacturer s instructions Maximum cable resistance Installation To install the FBI800 module complete the fol lowing steps 1 Set the optional jumper J2 to the desired set ting See Table 2 2 Set the optional SW3 DIP switches 5 6 to their default positions Refer to Table 3 CAUTION Do not connect the FBKD and TU directly to the serial FBF or serial FAT peripherals They ar...

Страница 3: ... to binary conversion Jumper 1 2 2 3 OPEN J2 RL1 Normally closed con tact Normally open con tact Table 2 Jumper setting for installation SW3 Function ON OFF 1 2 3 4 DIP1 DIP2 DIP3 DIP4 Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved 5 Boot Mode Active Disabled 6 Debug Mode Enabled Disabled 7 EA Door EA signal activates the FBKD door opener output EA signal doesn t acti vate...

Страница 4: ...ult Table 5 Optical indicators on the front panel RX1 Received data Bus1 left Green ON flickering Data is received on the Bus1 left channel OFF permanent Nothing is received on the Bus1 left channel TX1 Transmitted data Bus left Green ON flickering Data is transmitted on the Bus1 left channel OFF permanent Nothing is transmitted on the Bus1 left channel RX2 Received data Bus right Green ON flicker...

Страница 5: ...instructions Doc version 1 0 5 8 Wiring Serial FBF FAT FBI800 ERDE Ub1 XT1_5 PWR1 GND XT1_6 PWR1 Ub2 XT1_7 PWR2 GND XT1_8 PWR2 A2 XTI_3 REDB2 A B2 XTI_4 REDB2 B A1 XTI_1 REDB1 A B1 XT1_2 REDB1 B Table 7 Wiring of Schraner serial FBF FAT to FBI800 Transmit Unit FBI800 0V XT4_7 TU b 24V XT4 8 TUPWR RMS XT4_5 FIC b XT4_7 TU b a XT4_6 TU a Table 8 Wiring of Transmit Unit to FBI800 ...

Страница 6: ...4_4 TU OFF 7 8 XT4_2 AS OFF 9 10 XT3_5 TUACLED 11 XT3_1 CNOFLED 12 XT3_3 FIALLED 13 14 XT4_1 FIALRST 15 XT4_3 REV ON 16 BMZ A XT4_6 TU a BMZ B XT4_7 TU b UE A to Transmit Unit a UE B to Transmit Unit b Transmit Unit RMS XT4_5 FIC Table 9 Wiring of FBF 260 to FBI800 CAUTION Figure 4 is the parallel FBF installation example only The national standards and local regulations should be considered in th...

Страница 7: ...0 and FBF 260 FSD S3 FBI800 K1 XT2_7 SB LP K2 XT2_8 SB LP K3 K4 K5 XT2_3 DO PWR K6 XT2_4 DO PWR K7 XT2_5 DO CNT K8 XT2_6 DO CNT K9 XT2_1 HEAT K10 XT2_2 HEAT K11 XT2_9 SB LED K12 XT2_10 SB LED Table 10 Wiring of FSD S3 to FBI800 S24226 FBI800 FBF 260 X1 1 UE B b 0V X1 2 XT4_8 TU PWR X1 3 X1 4 XT4_5 FIC X1 5 UE B b 0V X1 6 UE A a Table 11 Wiring of Transmit Unit S24226 A12 by Siemens to FBI800 and F...

Страница 8: ...detection system Tyco Fire Security GmbH Victor von Bruns Strasse 21 8212 Neuhausen am Rheinfall Switzerland www zettlerfire com 120 515 292_PROFILE AP FBI800 F doc version 1 0 20 July 2017 Subject to change without notice ...